| Sensor elements |
temperature, radiation temperature, humidity, luminosity, motion |
| Measured values |
temperature, relative humidity, absolute humidity, enthalpy, dew point, luminosity, motion, radiation temperature |
| On stock |
No |
| Configuration |
uConfig, web interface |
| Network technology |
theGRID (RS485 Slave) |
| Operating range temperature (°C) |
0..50 |
| Operating ranges temperature (°C) |
0..+50 |
| Output signal temperature |
0..+50 °C |
| Operating range temperature enclosure (°C) |
0..+50 |
| Operating range humidity |
max. 95% rH non-condensing |
| Accuracy temperature |
±0,5 K (typ. at 21 °C) |
| Measuring range humidity |
0..100% rH non-condensing |
| Accuracy humidity |
±2% between 10..90% rH (typ. at 21 °C) |
| Measuring range light |
0..1000 Lux |
| Accuracy light |
±15 Lux, ±8% of measuring range |
| Dectection range |
detection range, angle 96° – with an installation height of 2,7 m circular detection range will have a Ø=6 m |
| Power supply |
24 V = (±10%) SELV |
| Enclosure |
PC V0 |
| Colour |
pure white |
| Protection (IP) |
IP30, according to EN 60529 |
| Connection |
removable plug-in terminal, max. 1,5 mm² |
| Mounting |
ceiling flush mount or with enclosure for surface mounting |
| Gefahrgut |
No |