Application/type |
Room operating unit |
Purpose |
Room Climate Control, Lighting control, Scene control, Shading control, Measure values |
Measured values |
temperature, relative humidity, absolute humidity, enthalpy, dew point, CO2, VOC, CO2/VOC mix |
Interface |
Casambi (BLE), RS485 Modbus, RS485 BACnet, KNX (TP) |
Functions |
temperature control, fan control, change-over, window/door monitoring, presence, lighting, blinds/shutter |
Operating functions |
setpoint adjustment temperature, fan stage adjustment, presence detection, light ON/OFF/DIM, blind UP/DOWN/SET, setup scenarios, ECO function, showing measured value and history |
Operating elements |
touch screen |
Configuration |
NOVOSapp, App, uConfig, BUS, ETS (KNX), (depending on type) |
Input |
1x input for NTC10k or floating contact, 1x input for floating contact, 2x input for floating contact |
Network technology |
RS485 Modbus, RS485 BACnet (MS/TP), KNX (TP1) |
Radio technology |
2,4 GHz, Casambi (BLE) |
Data transmission |
RTU, half-duplex, baud rate 9.600, 19.200, 38.400 or 57.600, parity: none (2 stop bits), even or odd (1 stop bit) |
Operating range temperature (°C) |
0..+50 |
Output signal temperature |
0..+50 °C (default setting), selectable from 4 temperature ranges -40..+60 | 0..+50 | -20..+80 | -15..+35 °C -50..+50 | 0..+50 | -20..+80 | -15..+35 °C, optionally configurable |
Operating range humidity |
max. 85% rH non-condensing |
Accuracy temperature |
±0,5 K (typ. at 21 °C), within default measuring range |
Measuring range humidity |
0..100% rH non-condensing, 0..85 KJ/kg enthalpy, 0..50 | 0..80 g/m³ absolute humidity, 0..+50 | -20..+80 °C dew point, optionally configurable |
Accuracy humidity |
±2% between 10..90% rH (typ. at 21 °C) |
Measuring range CO2 |
0..2000 ppm, 0..5000 ppm, optionally configurable |
Accuracy CO2 |
±50 ppm +3% of measured value (typ. at 21 °C, 50% rH, 1015 hPa), self-calibration Dual Channel |
Measuring VOC (mixed gas) |
heated metal oxide semiconductor |
Power supply |
24 V = (±10%) SELV, 24 V ~ (±10%) SELV |
Power consumption |
typ. 2,5 W (24 V =), 5 VA (24 V ~) |
Display |
TFT 4,8", 1120x480 px, capacitive touch technology |
Enclosure |
with thermal separation and sensor channel, PC V0 |
Colour |
pure white, black |
Protection (IP) |
IP30, according to EN 60529 |
Connection |
tool-free mountable spring clamp, max. 1,5 mm², removable plug-in terminal, max. Ø=0,8 mm, cable entry via rear opening, predetermined breaking point (bottom) or drilling mark (top) |
Mounting |
flush-mounted on standard EU box (Ø=60 mm), flush-mounted in standard EU box (Ø=60 mm, depth min. 45 mm), surface-mounted flat on base using adhesive foil or screws, base part can be mounted and wired separately |
Packaging length (mm) |
170 |
Packaging width (mm) |
110 |
Packaging height (mm) |
45 |
Packaging |
case packaging |
Device length (mm) |
163 |
Device width (mm) |
106 |
Device height (mm) |
25 |
Notes |
mixed gas sensors detect gases and vapours which can be oxidised (burnt): Body odours, tobacco smoke, exhalations emitted by materials (furniture, carpets, paint, glue ...) |
Gefahrgut |
No |