Room operating unit temperature, relative humidity | Active, 0..10 V | Room Climate Control, Measure values

Application/type Room operating unit
Purpose Room Climate Control, Measure values
Measured values temperature, relative humidity
Interface Active, 0..10 V
Functions temperature control
Operating functions setpoint adjustment temperature
Operating elements potentiometer (P), active 0..10 V, labelling of the manufacturer
Output voltage 2x 0..10 V, min. load 5 kΩ
Operating range temperature (°C) -35..+70
Operating ranges temperature (°C) -35..+70
Output signal temperature 0..+50 °C
Operating range humidity max. 85% rH non-condensing
Accuracy temperature ±1% of measuring range (typ. at 21 °C)
Measuring range humidity 0..100% rH non-condensing
Accuracy humidity ±2% between 10..90% rH (typ. at 21 °C)
Power supply 24 V = (±10%) SELV, 24 V ~ (±10%) SELV
Power consumption typ. 0,4 W (24 V =), 0,8 VA (24 V ~)
Enclosure central disc in design of the manufacturer
Colour white
Protection (IP) IP20, according to EN 60529
Connection terminal block, max. 1,5 mm²
Switch ranges Feller
Switch range Feller EDIZIOdue
Mounting flush-mounted in standard EU box (Ø=60 mm, depth min. 45 mm)
Delivery content incl. frame
Packaging length (mm) 90
Packaging width (mm) 90
Packaging height (mm) 80
Packaging case packaging
Device length (mm) 88
Device width (mm) 88
Device height (mm) 38
Weight (g) 50