Application/type Outdoor sensor
Purpose Measure values
Measured values temperature, relative humidity, absolute humidity, enthalpy, dew point, luminosity, atmospheric pressure
Interface Active, 0..5 V, 0..10 V, 4..20 mA, LON FT, Switch contact
On stock Yes
Configuration USEapp, App, uConfig, BUS, jumper, DIP switches, LoRaWAN® Downlink, (depending on type)
Sensor ambient light sensor with precise optical filtering appropriate to the human eye
Output voltage 0..10 V or 0..5 V, 2x 0..10 V or 0..5 V, 3x 0..10 V or 0..5 V, 4x 0..10 V or 0..5 V, adjustable via jumper, live-zero configuration via app or uConfig, min. load 10 kΩ
Output current 4..20 mA, 2x 4..20 mA, max. load 500 Ω
Output switch contact 2x floating contact NO for 24 V ~ or 24 V = / 3 A
Network technology RS485 Modbus, RS485 BACnet (MS/TP), LON FT (free topology)
Radio technology LoRaWAN® (868 MHz)
Data transmission bidirectional, RTU, half-duplex, baud rate 9.600, 19.200, 38.400 or 57.600, parity: none (2 stop bits), even or odd (1 stop bit)
Operating range temperature (°C) -30..+70
Operating ranges temperature (°C) -30..+70
Output signal temperature scaling analogue output, -20..+80 °C (default setting), selectable from 4 temperature ranges -40..+60 | 0..+50 | -20..+80 | -15..+35 °C, adjustable at the transducer, optionally configurable
Operating range humidity max. 85% rH short term condensation
Accuracy temperature ±0,4 K (typ. at 21 °C), ±0,5 K (typ. at 21 °C), within default measuring range, offset setting via app or uConfig
Measuring range humidity 0..100% rH non-condensing
Accuracy humidity ±2% between 10..90% rH (typ. at 21 °C), ±5% between 30..70% rH (typ. at 21 °C), offset setting via app or uConfig
Measuring range light 0..1000 lux (default setting), selectable from 6 ranges 0..200 lux | 0..1000 lux | 0..2 klux | 0..10 klux | 0..20 klux | 0..50 klux
Accuracy light ±5% of measuring range
Measuring range atm. pressure (hPa) 500..1500 hPa
Accuracy atmospheric pressure ±0,5% of measured value
Power supply 15..35 V = SELV, 19..29 V ~ SELV, battery type AA (2x)
Power consumption typ. 0,6 W (24 V =), 1,5 VA (24 V ~)
Enclosure USE-M, impact- and shock-resistant enclosure with quick-release cover, PC
Colour pure white, translucent cover PC
Protection (IP) IP65, according to EN 60529
Connection removable cable entry flextherm M20 for wire Ø=4,5..9 mm, removable cable entry M25 with fourfold cable entry for wire with max. Ø=7 mm, removable plug-in terminal, max. 2,5 mm², BUS max. 1,5 mm², relay max. 1,5 mm²
Delivery content incl. mounting base enclosure USE-M pure white, incl. mounting set (screws and accessories), incl. battery type AA (2x)