KFK03
KFK03 Pt100 150.08 3-wire
Duct sensor, Immersion sensor -50..+160 °C | Passive |
IP66 according to EN 60529 | Sensor probe, Ø=8 mm, stainless steel V4A (1.4571), length 158 mm, 150 mm
| Application/type | Duct sensor, Immersion sensor |
|---|---|
| Purpose | Measure values |
| Sensor elements | temperature |
| Measured values | temperature |
| Interface | Passive |
| On stock | No |
| Sensor | SI-Protection against permeation of humidity and mechanical stress (e.g. vibration), Pt100 DIN cl. B, passive |
| Operating range temperature (°C) | -50..+160 |
| Operating ranges temperature (°C) | -50..+160 |
| Operating range temperature enclosure (°C) | -35..+90 |
| Operating range humidity | max. 85% rH short term condensation |
| Accuracy temperature | ±0,3 K (typ. at 0 °C) |
| Material in touch with media | Sensor probe, Ø=8 mm, stainless steel V4A (1.4571), length 158 mm |
| Installation length (mm) | 150 |
| Enclosure | shape B, aluminium |
| Protection (IP) | IP66, according to EN 60529 |
| Connection | cable entry M20 for wire Ø=7 mm, terminal block, max. 1,5 mm² |
| Connection cable | 3-wire |
| Mounting | when used as duct sensors: please use mounting flange MF8 stainless steel, for use as immersion sensors please use immersion pocket THVA |
| Packaging length (mm) | 300 |
| Packaging width (mm) | 130 |
| Device length (mm) | 78 |
| Device width (mm) | 70 |
| Device height (mm) | 236 |
| Weight (g) | 250 |
| Gefahrgut | No |