| Application/type |
Differential pressure transducer |
| Purpose |
Measure values |
| Measured values |
differential pressure |
| Interface |
Active, 0..10 V, 4..20 mA |
| On stock |
Yes |
| Output voltage |
0..10 V, min. load 2 kΩ |
| Output current |
4..20 mA, max. load 900 Ω |
| Operating range temperature (°C) |
-20..+80 |
| Operating ranges temperature (°C) |
-20..+80 |
| Operating range temperature enclosure (°C) |
-20..+50 |
| Operating range humidity |
max. 85% rH short term condensation |
| Operating range pressure |
max. 6 bar, max. 16 bar, fluids |
| Measuring range pressure |
0..1 bar, 0..2,5 bar, 0..4 bar, 0..6 bar |
| Accuracy pressure |
±1% of measuring range (typ. at -5..+75 °C) |
| Power supply |
15..24 V = (±10%) SELV, 24 V ~ (±10%) SELV |
| Power consumption |
typ. 0,37 W (24 V =), max. 0,5 W (24 V =), 0,9 VA (24 V ~) |
| Material in touch with media |
stainless steel, G1/4" |
| Enclosure |
stainless steel V2A (1.4305), lid die-cast aluminium, measuring cell ceramic |
| Colour |
black |
| Protection (IP) |
IP54, according to EN 60529 |
| Connection |
angle plug DIN 43650, type A |
| Packaging length (mm) |
170 |
| Packaging width (mm) |
120 |
| Device length (mm) |
67 |
| Device width (mm) |
30 |
| Device height (mm) |
94 |
| Catalogue table |
Differential pressure transducer |
| Gefahrgut |
No |