Application/type |
Pressure transducer |
Purpose |
Measure values |
Measured values |
pressure |
Interface |
Active, 0..10 V, 4..20 mA |
Output voltage |
0..10 V, min. load 5 kΩ |
Output current |
4..20 mA, max. load 500 Ω |
Operating range temperature (°C) |
-40..+125 |
Operating ranges temperature (°C) |
-40..+125 |
Operating range temperature enclosure (°C) |
-40..+105 |
Operating range pressure |
fluids, air or other non-flammable/non-aggressive gases |
Measuring range pressure |
-1..0 bar, 0..1 bar, 0..1,6 bar, 0..2 bar, 0..2,5 bar, 0..4 bar, 0..6 bar, 0..10 bar, 0..16 bar, 0..25 bar, 0..40 bar, 0..60 bar, 0..100 bar |
Accuracy pressure |
±0,5% (typ. at 21 °C) |
Power supply |
15..24 V = (±10%) SELV, 24 V ~ (±10%) SELV |
Power consumption |
typ. 0,15 W (24 V =), typ. 0,5 W (24 V =), 0,3 VA (24 V ~) |
Material in touch with media |
stainless steel V2A (1.4305), G1/2", G1/4" |
Protection (IP) |
IP65, according to EN 60529 |
Connection |
cable gland for wires with Ø=8 mm max., plug MVS according to DIN 175301-803 |
Packaging length (mm) |
170 |
Packaging width (mm) |
120 |
Device length (mm) |
50 |
Device width (mm) |
35 |
Weight (g) |
60 |
Catalogue table |
Pressure transducer |
Gefahrgut |
No |