Thermokon
155.70 EUR
(plus surcharge required accessory)
Item No.: 839204
Group: R2
Add to comparison list Add to project Show accessories

WRF07 x

WRF07 P temp RS485 Modbus ltype2 pure white

Room operating unit temperature | RS485 Modbus | Room Climate Control, Measure values

Application/type Room operating unit
Purpose Room Climate Control, Measure values
Sensor elements temperature
Measured values temperature
Interface RS485 Modbus
On stock No
Operating functions setpoint adjustment temperature
Operating elements potentiometer (P)
Configuration BUS, DIP switches
Input 2x input digital for floating switch contact
Network technology RS485 Modbus
Data transmission RTU, half-duplex, baud rate 9.600, 19.200, 38.400 or 57.600, parity: none (2 stop bits), even or odd (1 stop bit)
Operating range temperature (°C) 0..+50
Operating ranges temperature (°C) 0..+50
Output signal temperature 0..+50 °C
Operating range humidity max. 85% rH non-condensing
Accuracy temperature ±0,5 K (typ. at 21 °C)
Power supply 15..35 V = SELV, 19..29 V ~ SELV
Power consumption max. 1,6 W (24 V =), 3,9 VA (24 V ~)
Colour pure white
Protection (IP) IP30, according to EN 60529
Connection terminal block, max. 1,5 mm²
Switch ranges Berker, Busch-Jaeger, Feller, Gira, Jung, Merten, (please specify the desired frame when ordering)
Switch range Berker S.1, B.3 aluminium, B.7, B.7 glass, Q.1, Q.3, K.5 aluminium/stainless steel
Switch range Busch-Jaeger alpha nea®, Busch-axcent®, Busch-balance® SI, Busch-Duro 2000® SI, impuls, Reflex SI, solo®
Switch range Feller EDIZIOdue, STANDARDdue
Switch range Gira E2, E3, Esprit, Event, Flächenschalter, Standard 55
Switch range Jung A 500, A 550, A creation, A plus, AS 500, CD 500, LS 990
Switch range Merten 1-M, Antik, Artec, Artec stainless steel, Atelier-M, M-Arc, M-Plan, M-Pure, M-Smart
Switch range Peha Aura, Aura glass
Mounting flush-mounted in standard EU box (Ø=60 mm, depth min. 45 mm)
Packaging length (mm) 90
Packaging width (mm) 90
Packaging height (mm) 80
Packaging case packaging
Device length (mm) 81
Device width (mm) 81
Device height (mm) 38
Weight (g) 50
Notes Mixed-gas sensors detect volatile organic compounds (VOC) such as body odours, tobacco smoke and off-gassing from materials (furniture, carpets, paint, adhesives, etc.)
Gefahrgut No
155.70 EUR
(plus surcharge required accessory)
Item No.: 839204
Group: R2
Add to comparison list Add to project Show accessories
Top