WRF06 CO2+VOC temp_rH 4xV Jung LS 990 pure white brilliant/alpin white

Room sensor temperature, relative humidity, CO2, VOC, CO2/VOC mix | Active, 0..10 V | 0..+50 °C
0..2000 ppm NDIR (non-dispersive, infrared)

Application/type Room sensor
Purpose Measure values
Measured values temperature, relative humidity, CO2, VOC, CO2/VOC mix
Interface Active, 0..10 V
Sensor NDIR (non-dispersive, infrared)
Output voltage 4x 0..10 V, min. load 10 kΩ
Operating range temperature (°C) 0..+50
Operating ranges temperature (°C) 0..+50
Output signal temperature scaling analogue output, 0..+50 °C
Operating range humidity max. 85% rH non-condensing
Accuracy temperature ±0,5 K (typ. at 21 °C)
Measuring range CO2 0..2000 ppm
Accuracy CO2 ±50 ppm +3% of measured value (typ. at 21 °C, 50% rH, 1015 hPa), self-calibration Dual Channel
Measuring VOC (mixed gas) heated metal oxide semiconductor, self-calibration
Power supply 15..24 V = (±10%) SELV, 24 V ~ (±10%) SELV
Power consumption max. 1,6 W (24 V =), 3,9 VA (24 V ~)
Enclosure PC, central disc Thermokon (frame selectable)
Colour pure white brilliant
Protection (IP) IP30, according to EN 60529
Connection terminal block, max. 1,5 mm², pluggable, cable entry via rear opening
Switch ranges Jung
Switch range Jung LS 990 with intermediate frame
Mounting flush-mounted in standard EU box (Ø=60 mm, depth min. 45 mm)
Delivery content incl. frame
Packaging length (mm) 90
Packaging width (mm) 90
Packaging height (mm) 80
Packaging case packaging
Device length (mm) 77
Device width (mm) 77
Device height (mm) 46