Thermokon
268.00 EUR
Item No.: 704519
Group: AQ1
Add to comparison list Add to project Show accessories

WRF06

WRF06 CO2 V EDIZIOdue white

Room sensor CO2 | Active, 0..10 V | 0..+50 °C
0..2000 ppm NDIR (non-dispersive, infrared)

Application/type Room sensor
Purpose Measure values
Measured values CO2
Interface Active, 0..10 V
Sensor NDIR (non-dispersive, infrared)
Output voltage 0..10 V, min. load 10 kΩ
Operating range temperature (°C) 0..+50
Operating ranges temperature (°C) 0..+50
Operating range humidity max. 85% rH non-condensing
Measuring range CO2 0..2000 ppm
Accuracy CO2 ±50 ppm +3% of measured value (typ. at 21 °C, 50% rH, 1015 hPa), self-calibration Dual Channel
Power supply 15..24 V = (±10%) SELV, 24 V ~ (±10%) SELV
Power consumption max. 1,6 W (24 V =), 3,9 VA (24 V ~)
Enclosure PC, central disc Thermokon (frame selectable)
Colour white
Protection (IP) IP30, according to EN 60529
Connection terminal block, max. 1,5 mm², pluggable, cable entry via rear opening
Switch ranges Feller
Switch range Feller EDIZIOdue
Mounting flush-mounted in standard EU box (Ø=60 mm, depth min. 45 mm)
Delivery content incl. frame
Packaging length (mm) 90
Packaging width (mm) 90
Packaging height (mm) 80
Packaging case packaging
Device length (mm) 88
Device width (mm) 88
Device height (mm) 38