Thermokon
278.80 EUR
Item No.: 803755
Group: AQ1
Add to comparison list Add to project Show accessories

WRF06

WRF06 CO2 temp VV EDIZIOdue black

Room sensor temperature, CO2 | Active, 0..10 V | 0..+50 °C
0..2000 ppm NDIR (non-dispersive, infrared)

Application/type Room sensor
Purpose Measure values
Measured values temperature, CO2
Interface Active, 0..10 V
Sensor NDIR (non-dispersive, infrared)
Output voltage 2x 0..10 V, min. load 10 kΩ
Operating range temperature (°C) 0..+50
Operating ranges temperature (°C) 0..+50
Output signal temperature scaling analogue output, 0..+50 °C
Operating range humidity max. 85% rH non-condensing
Accuracy temperature ±0,5 K (typ. at 21 °C)
Measuring range CO2 0..2000 ppm
Accuracy CO2 ±50 ppm +3% of measured value (typ. at 21 °C, 50% rH, 1015 hPa), self-calibration Dual Channel
Power supply 15..24 V = (±10%) SELV, 24 V ~ (±10%) SELV
Power consumption max. 1,6 W (24 V =), 3,9 VA (24 V ~)
Enclosure PC, central disc Thermokon (frame selectable)
Colour black
Protection (IP) IP30, according to EN 60529
Connection terminal block, max. 1,5 mm², pluggable, cable entry via rear opening
Switch ranges Feller
Switch range Feller EDIZIOdue
Mounting flush-mounted in standard EU box (Ø=60 mm, depth min. 45 mm)
Delivery content incl. frame
Packaging length (mm) 90
Packaging width (mm) 90
Packaging height (mm) 80
Packaging case packaging
Device length (mm) 88
Device width (mm) 88
Device height (mm) 38
278.80 EUR
Item No.: 803755
Group: AQ1
Add to comparison list Add to project Show accessories
Top