Thermokon
84.30 EUR
Item No.: 747806
Group: TP2
Add to comparison list Add to project Show accessories

VFG54+

VFG54+ Basic RS485 Modbus

Contact sensor -35..+120 °C | RS485 Modbus | Sensor probe, brass, spring loaded sensor
along the pipe or sideways

Application/type Contact sensor
Purpose Measure values
Measured values temperature
Interface RS485 Modbus
Configuration BUS, DIP switches
Sensor SI-Protection against permeation of humidity and mechanical stress (e.g. vibration)
Network technology RS485 Modbus
Data transmission RTU, half-duplex, baud rate 9.600, 19.200, 38.400 or 57.600, parity: none (2 stop bits), even or odd (1 stop bit)
Operating range temperature (°C) -35..+120
Operating ranges temperature (°C) -35..+120
Operating range temperature enclosure (°C) -35..+70
Operating range humidity max. 85% rH short term condensation
Accuracy temperature ±0,5 K (typ. at 21 °C)
Power supply 15..24 V = (±10%) SELV, 24 V ~ (±10%) SELV
Power consumption max. 0,7 W (24 V =), 1,8 VA (24 V ~)
Material in touch with media Sensor probe, brass, spring loaded sensor
Enclosure USE-S, impact- and shock-resistant enclosure with quick-release cover, PC
Colour pure white
Protection (IP) IP65, according to EN 60529
Connection removable cable entry flextherm M20 for wire Ø=4,5..9 mm, removable plug-in terminal, max. 2,5 mm²
Mounting along the pipe or sideways
Packaging length (mm) 105
Packaging width (mm) 85
Packaging height (mm) 54
Packaging case packaging
Device length (mm) 63
Device width (mm) 68
Device height (mm) 90