Thermokon
642.00 EUR
Item No.: 780803
Group: RU1
Add to comparison list Add to project Show accessories

NOVOS Touch

NOVOS Touch white CO2+VOC temp_rH KNX

Room operating unit temperature, relative humidity, absolute humidity, enthalpy, dew point, VOC | KNX (TP)
Room Climate Control, Lighting control, Scene control, Shading control, Measure values

Application/type Room operating unit
Purpose Room Climate Control, Lighting control, Scene control, Shading control, Measure values
Measured values temperature, relative humidity, absolute humidity, enthalpy, dew point, VOC
Interface KNX (TP)
Functions temperature control, fan control, change-over, window/door monitoring, presence, lighting, blinds/shutter
Operating functions setpoint adjustment temperature, fan stage adjustment, presence detection, light ON/OFF/DIM, blind UP/DOWN/SET, setup scenarios, ECO function, showing measured value and history
Operating elements touch screen
Configuration NOVOSapp, uConfig, BUS, ETS (KNX)
Input 1x input for NTC10k or floating contact, 2x input for floating contact
Network technology KNX (TP1)
Operating range temperature (°C) 0..+50
Operating ranges temperature (°C) 0..+50
Output signal temperature 0..+50 °C
Operating range humidity max. 85% rH non-condensing
Accuracy temperature ±0,5 K (typ. at 21 °C), within default measuring range
Measuring range humidity 0..100% rH non-condensing, 0..85 KJ/kg enthalpy, 0..50 | 0..80 g/m³ absolute humidity, 0..+50 | -20..+80 °C dew point, optionally configurable
Accuracy humidity ±2% between 10..90% rH (typ. at 21 °C)
Measuring VOC (mixed gas) heated metal oxide semiconductor
Power supply 24 V = (±10%) SELV
Power consumption typ. 2,5 W (24 V =)
Display TFT 4,8", 1120x480 px, capacitive touch technology
Enclosure with thermal separation and sensor channel, PC V0
Colour pure white
Protection (IP) IP30, according to EN 60529
Connection removable plug-in terminal, max. Ø=0,8 mm, cable entry via rear opening
Mounting flush-mounted in standard EU box (Ø=60 mm, depth min. 45 mm), base part can be mounted and wired separately
Packaging length (mm) 170
Packaging width (mm) 110
Packaging height (mm) 45
Packaging case packaging
Device length (mm) 163
Device width (mm) 106
Device height (mm) 46
Notes mixed gas sensors detect gases and vapours which can be oxidised (burnt): Body odours, tobacco smoke, exhalations emitted by materials (furniture, carpets, paint, glue ...), KNX certification: pending