NOVOS 5
NOVOS 5 CO2 temp_rH white LCD 3xA
Room sensor temperature, relative humidity, absolute humidity, enthalpy, dew point, CO2 | Active, 4..20 mA | 0..+50 °C
0..2000 ppm, 0..5000 ppm, optionally configurable
Application/type | Room sensor |
---|---|
Purpose | Measure values |
Measured values | temperature, relative humidity, absolute humidity, enthalpy, dew point, CO2 |
Interface | Active, 4..20 mA |
Configuration | USEapp, uConfig |
Output current | 3x 4..20 mA, max. load 500 Ω |
Operating range temperature (°C) | 0..+50 |
Operating ranges temperature (°C) | 0..+50 |
Output signal temperature | 0..+50 °C (default setting), selectable from 4 temperature ranges -40..+60 | 0..+50 | -20..+80 | -15..+35 °C -50..+50 | 0..+50 | -20..+80 | -15..+35 °C, optionally configurable |
Operating range humidity | max. 85% rH non-condensing |
Accuracy temperature | ±0,5 K (typ. at 21 °C) |
Measuring range CO2 | 0..2000 ppm, 0..5000 ppm, optionally configurable |
Accuracy CO2 | ±50 ppm +3% of measured value (typ. at 21 °C, 50% rH, 1015 hPa), self-calibration Dual Channel |
Power supply | 15..35 V = SELV |
Power consumption | max. 0,5 W (24 V =) |
Display | LCD 29x35 mm, RGB backlight, with traffic light function, threshold values configurable, optionally configurable via app or uConfig |
Enclosure | PC V0 |
Colour | pure white |
Protection (IP) | IP30, according to EN 60529 |
Connection | tool-free mountable spring clamp, max. 1,5 mm², cable entry via rear opening, predetermined breaking point (bottom) or drilling mark (top) |
Mounting | flush-mounted on standard EU box (Ø=60 mm), surface-mounted flat on base using adhesive foil or screws, base part can be mounted and wired separately |
Packaging length (mm) | 170 |
Packaging width (mm) | 110 |
Packaging height (mm) | 45 |
Device length (mm) | 163 |
Device width (mm) | 106 |
Device height (mm) | 25 |