NOVOS 5

Active room sensor in the NOVOS 5 enclosure for measurement of temperature, humidity (relative and absolute humidity, enthalpy, dew point), CO2 and mixed gas (VOC) depending on the variant. The maintenance-free sensor contributes to a pleasant room climate and well-being. Typical applications include schools, office buildings, hotels or cinemas. The NOVOS 5 uses an LCD with color-changing backlight for displaying the measured values and exceeding threshold values. Different parameters like the display settings can be individually configured via Thermokon NOVOSapp. Optionally, operating elements for controlling HVAC systems can be added (see product NOVOS 5 x in the chapter 'Room Operating Units').

Application/type Room sensor
Purpose Measure values
Measured values temperature, relative humidity, absolute humidity, enthalpy, dew point, CO2, VOC, CO2/VOC mix
Interface RS485 Modbus, RS485 BACnet, KNX (TP), Passive, Active, 0..5 V, 0..10 V, 4..20 mA
Functions integrated PI and two-position controller
Configuration NOVOSapp, uConfig, BUS, ETS (KNX), (depending on type)
Output voltage 0..10 V or 0..5 V, 2x 0..10 V or 0..5 V, 3x 0..10 V or 0..5 V, 4x 0..10 V or 0..5 V, adjustable via jumper, live-zero configuration via app or uConfig, min. load 10 kΩ
Output current 4..20 mA, 2x 4..20 mA, 3x 4..20 mA, 4x 4..20 mA, max. load 500 Ω
Input 1x input for NTC10k or floating contact, 1x input for floating contact, 2x input for floating contact
Network technology RS485 Modbus, RS485 BACnet (MS/TP), KNX (TP1)
Data transmission RTU, half-duplex, baud rate 9.600, 19.200, 38.400 or 57.600, parity: none (2 stop bits), even or odd (1 stop bit)
Operating range temperature (°C) 0..+50
Output signal temperature 0..+50 °C (default setting), selectable from 4 temperature ranges -40..+60 | 0..+50 | -20..+80 | -15..+35 °C -50..+50 | 0..+50 | -20..+80 | -15..+35 °C, optionally configurable
Operating range humidity max. 85% rH non-condensing
Accuracy temperature ±0,5 K (typ. at 21 °C)
Measuring range humidity 0..100% rH non-condensing, 0..85 KJ/kg enthalpy, 0..50 | 0..80 g/m³ absolute humidity, 0..+50 | -20..+80 °C dew point, optionally configurable
Accuracy humidity ±2% between 10..90% rH (typ. at 21 °C)
Measuring range CO2 0..2000 ppm, 0..5000 ppm, optionally configurable
Accuracy CO2 ±50 ppm +3% of measured value (typ. at 21 °C, 50% rH, 1015 hPa), self-calibration Dual Channel
Measuring VOC (mixed gas) heated metal oxide semiconductor
Power supply 24 V = (±10%) SELV, 15..35 V = SELV, 19..29 V ~ SELV
Power consumption typ. 0,4 W (24 V =), 0,8 VA (24 V ~), max. 0,5 W (24 V =)
Display LCD 29x35 mm, RGB backlight, with traffic light function, threshold values configurable, optionally configurable via app or uConfig
Enclosure PC V0
Colour pure white, aluminium, black
Protection (IP) IP30, according to EN 60529
Connection tool-free mountable spring clamp, max. 1,5 mm², removable plug-in terminal, max. Ø=0,8 mm, cable entry via rear opening, predetermined breaking point (bottom) or drilling mark (top)
Mounting flush-mounted on standard EU box (Ø=60 mm), flush-mounted in standard EU box (Ø=60 mm, depth min. 45 mm), surface-mounted flat on base using adhesive foil or screws, base part can be mounted and wired separately
Packaging length (mm) 170
Packaging width (mm) 110
Packaging height (mm) 45
Device length (mm) 163
Device width (mm) 106
Device height (mm) 25
Notes mixed gas sensors detect gases and vapours which can be oxidised (burnt): Body odours, tobacco smoke, exhalations emitted by materials (furniture, carpets, paint, glue ...)