Filter


Reset
Show item

Surface Sensors

OF14

Surface-mounted sensor for temperature measurement on glass or similar surfaces. Designed for connecting to controls and display systems.

Application/type Cable sensor, Surface sensor
Purpose Measure values
Measured values temperature
Interface Passive
Sensor SI-Protection against permeation of humidity and mechanical stress (e.g. vibration), PT1000 DIN Kl. B, PT100 DIN Kl. B, PT1000 1/3 DIN, PT100 1/3 DIN, Ni1000 DIN Kl. B, Ni1000TK5000, NTC10k, NTC10k Precon, NTC20K, NTC1,8K, NTC5K, LM235Z, passive
Operating range temperature (°C) -35..+70
Operating range humidity max. 85% rH short term condensation
Accuracy temperature ±0,5 K (typ. at 21 °C), within default measuring range, ±0,3 K (typ. at 0 °C), ±0,4 K (typ. at 0 °C), ±0,22 K (typ. at 25 °C), depending on length of connection wire and sensor
Material in touch with media Sensor probe, aluminium, 35x10x6 mm
Installation length (mm) 35
Enclosure USE-S, impact- and shock-resistant enclosure with quick-release cover, PC, USE-M, impact- and shock-resistant enclosure with quick-release cover, PC
Colour pure white
Protection (IP) IP65, according to EN 60529
Connection removable cable entry flextherm M20 for wire Ø=4,5..9 mm, removable plug-in terminal, max. 2,5 mm²
Connection cable PVC, 0,25 mm², 2-wire, white
Length connection wire (m) 1, 2, 4, 6
Mounting surface mounting due to self-adhesive sensor surface
Delivery content incl. mounting base enclosure USE-S pure white, incl. mounting set (screws and accessories)
Comparison list
Top