Filter
Discontinued
MWF+ LON
Duct sensor for measuring the average temperature in air ducts. The sensor measures the mean temperature value throughout the entire length. A spring at the connection head reduces vibrations. Mounting angles are included in the delivery content. Models with a relay output for a 2-point controller or a 2-stage 2-point controller and color-changing LCD allow for a wide range of applications. A hinged cover and tool-free wiring as well as removable cable entries ensure a quick and easy installation.
| Application/type | Duct averaging sensor |
|---|---|
| Purpose | Measure values |
| Measured values | temperature |
| Interface | LoRaWAN® (868 MHz), RS485 Modbus, RS485 BACnet, LON FT, Passive, Active, 0..5 V, 0..10 V, 4..20 mA, Switch contact |
| On stock | Yes |
| Configuration | USEapp, uConfig, BUS, jumper, DIP switches, LoRaWAN® Downlink, (depending on type) |
| Sensor | Pt1000 DIN cl. B, Ni1000 DIN cl. B, Ni1000TK5000, Ni891, NTC10k, NTC10k Precon, NTC20k, passive |
| Output voltage | 0..10 V or 0..5 V, adjustable via jumper, live-zero configuration via app or uConfig, min. load 5 kΩ, min. load 10 kΩ |
| Output current | 4..20 mA, max. load 500 Ω |
| Output switch contact | 2x floating contact NO for 24 V ~ or 24 V = / 3 A |
| Network technology | RS485 Modbus, RS485 BACnet (MS/TP), LON FT (free topology) |
| Radio technology | LoRaWAN® (868 MHz) |
| Data transmission | bidirectional, RTU, half-duplex, baud rate 9.600, 19.200, 38.400 or 57.600, parity: none (2 stop bits), even or odd (1 stop bit) |
| Operating range temperature (°C) | -30..+70 |
| Operating ranges temperature (°C) | 0..+50, -30..+70 |
| Output signal temperature | scaling analogue output, -20..+80 °C (default setting), selectable from 4 temperature ranges -50..+50 | -20..+80 | -15..+35 | -10..+120 | 0..+50 | 0..+100 | 0..+160 | 0..+250 °C, adjustable at the transducer, optionally configurable via app or uConfig |
| Operating range temperature enclosure (°C) | -30..+70, -20..+70 |
| Operating range humidity | max. 85% rH short term condensation |
| Accuracy temperature | ±0,5 K (typ. at 21 °C), within default measuring range, ±0,4 K (typ. at 0 °C), ±0,2 K (typ. at 25 °C, temperature dependend), potentiometer for offset adjustment, offset setting via app or uConfig |
| Power supply | 15..24 V = (±10%) SELV, 15..35 V = SELV, 24 V ~ (±10%) SELV, 19..29 V ~ SELV |
| Power consumption | typ. 0,4 W (24 V =), typ. 0,5 W (24 V =), max. 2,5 W (24 V =), 0,8 VA (24 V ~), 4,3 VA (24 V ~) |
| Material in touch with media | Sensor rod, measures the mean temperature value throughout the entire length of the sensor rod, measures the mean temperature value selectively throughout the length of the sensor rod |
| Installation length (mm) | 3000, 6000 |
| Display | LCD 29x35 mm, RGB backlight, with traffic light function, threshold values configurable, optionally configurable via app or uConfig |
| Enclosure | USE-S, impact- and shock-resistant enclosure with quick-release cover, PC, USE-M, impact- and shock-resistant enclosure with quick-release cover, PC |
| Colour | pure white, transparent cover |
| Protection (IP) | IP65, according to EN 60529 |
| Connection | removable cable entry flextherm M20 for wire Ø=4,5..9 mm, removable cable entry M25 with fourfold cable entry for wire with max. Ø=7 mm, removable plug-in terminal, max. 2,5 mm², BUS max. 1,5 mm², relay max. 1,5 mm² |
| Delivery content | incl. mounting flange, incl. mounting set (screws and accessories), incl. installation set |
| Packaging length (mm) | 220 |
| Packaging width (mm) | 310 |
| Notes | external antenna available on request |
| Gefahrgut | No |
| Vorschau | Name |
|---|---|
|
|
MWF-Plus_Header.jpg |