| Application/type |
Duct sensor |
| Purpose |
Measure values |
| Measured values |
temperature, relative humidity, absolute humidity, enthalpy, dew point |
| Interface |
RS485 Modbus, Active, 0..5 V, 0..10 V |
| On stock |
No |
| Configuration |
USEapp, uConfig, BUS, jumper, DIP switches |
| Output voltage |
2x 0..10 V or 0..5 V, adjustable via jumper, live-zero configuration via app or uConfig, min. load 10 kΩ |
| Network technology |
RS485 Modbus |
| Data transmission |
RTU, half-duplex, baud rate 9.600, 19.200, 38.400 or 57.600, parity: none (2 stop bits), even or odd (1 stop bit) |
| Operating range temperature (°C) |
-20..+70 |
| Output signal temperature |
scaling analogue output, -20..+80 °C (default setting), selectable from 4 temperature ranges -40..+60 | 0..+50 | -20..+80 | -15..+35 °C, optionally configurable |
| Operating range humidity |
max. 85% rH short term condensation |
| Accuracy temperature |
±0,3 K (typ. at 21 °C), within default measuring range, offset setting via app or uConfig |
| Measuring range humidity |
0..100% rH non-condensing, 0..85 KJ/kg enthalpy, 0..50 | 0..80 g/m³ absolute humidity, 0..+50 | -20..+80 °C dew point, optionally configurable |
| Accuracy humidity |
±2% between 10..90% rH (typ. at 21 °C), offset setting via app or uConfig |
| Power supply |
15..35 V = SELV, 19..29 V ~ SELV |
| Power consumption |
typ. 0,4 W (24 V =), max. 2,5 W (24 V =), 0,8 VA (24 V ~), 4,3 VA (24 V ~) |
| Material in touch with media |
Pipe, PA6, with filter stainless steel wire mesh, black, Ø=19,5 mm |
| Installation length (mm) |
140, 270, 400 |
| Display |
LCD 29x35 mm, RGB backlight, with traffic light function, threshold values configurable, optionally configurable via app or uConfig |
| Enclosure |
USE-M, impact- and shock-resistant enclosure with quick-release cover, PC |
| Colour |
pure white, transparent cover |
| Protection (IP) |
IP65, according to EN 60529 |
| Connection |
removable cable entry M25 with fourfold cable entry for wire with max. Ø=7 mm, removable plug-in terminal, max. 2,5 mm², BUS max. 1,5 mm² |
| Delivery content |
incl. mounting flange, incl. mounting set (screws and accessories) |
| Notes |
air speed max. 12 m/s |
| Gefahrgut |
No |