| Application/type |
Outdoor sensor |
| Purpose |
Measure values |
| Measured values |
temperature |
| Interface |
LoRaWAN® (868 MHz), Active, 0..5 V, 0..10 V |
| On stock |
No |
| Configuration |
USEapp, uConfig, jumper, LoRaWAN® Downlink |
| Sensor |
SI-Protection against permeation of humidity and mechanical stress (e.g. vibration) |
| Output voltage |
0..10 V or 0..5 V, adjustable via jumper, live-zero configuration via app or uConfig, min. load 10 kΩ |
| Radio technology |
LoRaWAN® (868 MHz) |
| Data transmission |
bidirectional |
| Operating range temperature (°C) |
-35..+90 |
| Operating ranges temperature (°C) |
-35..+70, -20..+70 |
| Output signal temperature |
scaling analogue output, -20..+80 °C (default setting), selectable from 4 temperature ranges -50..+50 | -20..+80 | -15..+35 | -10..+120 | 0..+50 | 0..+100 | 0..+160 | 0..+250 °C, optionally configurable |
| Accuracy temperature |
±0,5 K (typ. at 21 °C), within default measuring range, offset setting via app or uConfig |
| Power supply |
15..35 V = SELV, 19..29 V ~ SELV |
| Power consumption |
max. 2,5 W (24 V =), 4,3 VA (24 V ~) |
| Material in touch with media |
Sensor probe, Ø=6 mm, stainless steel V2A (1.4305), length 25 mm, for faster response |
| Enclosure |
USE-M, impact- and shock-resistant enclosure with quick-release cover, PC |
| Colour |
pure white |
| Protection (IP) |
IP65, according to EN 60529 |
| Connection |
removable cable entry M25 with fourfold cable entry for wire with max. Ø=7 mm, removable plug-in terminal, max. 2,5 mm² |
| Delivery content |
incl. mounting base enclosure USE-M pure white, incl. mounting set (screws and accessories) |
| Packaging |
case packaging |
| Notes |
external antenna available on request |
| Gefahrgut |
No |