Filter


Reset
Show item

Contact Sensors

AF25

Contact sensor with connection cable and brass strap for surface temperature measurement (cold or hot water) on pipes and other curved surfaces.

Application/type Contact sensor, Cable sensor
Purpose Measure values
Measured values temperature
Interface Passive
Sensor SI-Protection against permeation of humidity and mechanical stress (e.g. vibration), PT1000 DIN Kl. B, PT100 DIN Kl. B, PT1000 1/3 DIN, PT100 1/3 DIN, Ni1000 DIN Kl. B, Ni1000TK5000, NTC10k, NTC10k Precon, NTC10K Carel, NTC20K, NTC1,8K, NTC5K, passive
Operating range temperature (°C) -50..+135
Operating ranges temperature (°C) -35..+100, -50..+135
Operating range temperature enclosure (°C) -35..+90
Operating range humidity max. 85% rH short term condensation
Accuracy temperature ±0,1 K (typ. at 0 °C), ±0,3 K (typ. at 0 °C), ±0,4 K (typ. at 0 °C), ±0,2 K (typ. at 25 °C), ±0,22 K (typ. at 25 °C), ±0,26 K (typ. at 25 °C), see characteristic curve
Material in touch with media Sensor probe, Ø=6 mm, brass, with contact tongue, 16-point pressed (IP65)
Installation length (mm) 35
Protection (IP) IP65, according to EN 60529
Connection cable PVC, silicone, 0,25 mm², 2-wire, 3-wire, 4-wire
Length connection wire (m) 1, 2, 4, 6
Comparison list

Items

Top