WRF06 INC
WRF06 INC temp RS485 Modbus Merten M-Smart polar white brilliant
Room operating unit temperature | RS485 Modbus | Room Climate Control, Measure values
Application/type | Room operating unit |
---|---|
Purpose | Room Climate Control, Measure values |
Measured values | temperature |
Interface | RS485 Modbus |
Functions | temperature control |
Operating functions | setpoint adjustment temperature, fan stage adjustment, standby/presence detection, ECO function, status feedback via LED |
Operating elements | rotary encoder/push button for setpoint adjustment/ECO function, labelling {ice crystal [tail] [tail] heating symbol} |
Configuration | BUS, DIP switches |
Input | 1x input for NTC10k or floating contact |
Network technology | RS485 Modbus |
Data transmission | RTU, half-duplex, baud rate 9.600, 19.200, 38.400 or 57.600, parity: none (2 stop bits), even or odd (1 stop bit) |
Operating range temperature (°C) | -10..+50 |
Operating ranges temperature (°C) | -10..+50 |
Output signal temperature | 0..+50 °C |
Operating range humidity | max. 85% rH non-condensing |
Accuracy temperature | ±0,3 K (typ. at 21 °C) |
Power supply | 15..24 V = (±10%) SELV, 24 V ~ (±10%) SELV |
Power consumption | typ. 0,3 W (24 V =), 0,9 VA (24 V ~) |
Display | 7 LEDs for displaying setpoint adjustment, LED for displaying the ECO mode function |
Enclosure | PA6.6 |
Colour | polar white brilliant |
Protection (IP) | IP30, according to EN 60529 |
Connection | terminal block, max. 1,5 mm², pluggable |
Switch ranges | Merten |
Switch range Merten | M-Smart |
Mounting | flush-mounted in standard EU box (Ø=60 mm, depth min. 45 mm) |
Packaging length (mm) | 90 |
Packaging width (mm) | 90 |
Packaging height (mm) | 80 |
Packaging | case packaging |
Device length (mm) | 81 |
Device width (mm) | 81 |
Device height (mm) | 53 |
Notes | price including frame (Berker S.1, Merten M-Smart or Merten M-Plan) |