VFG54+
VFG54+ LCD TRA MultiRange
Contact sensor -35..+120 °C | Active, 4..20 mA | Sensor probe, brass, spring loaded sensor
along the pipe or sideways
Application/type | Contact sensor |
---|---|
Purpose | Measure values |
Measured values | temperature |
Interface | Active, 4..20 mA |
Configuration | USEapp, uConfig |
Sensor | SI-Protection against permeation of humidity and mechanical stress (e.g. vibration) |
Operating range temperature (°C) | -35..+120 |
Operating ranges temperature (°C) | -35..+120 |
Output signal temperature | scaling analogue output, -20..+80 °C (default setting), selectable from 4 temperature ranges -50..+50 | -20..+80 | -15..+35 | -10..+120 | 0..+50 | 0..+100 | 0..+160 | 0..+250 °C, optionally configurable |
Operating range temperature enclosure (°C) | -20..+70 |
Operating range humidity | max. 85% rH short term condensation |
Accuracy temperature | ±0,5 K (typ. at 21 °C), within default measuring range, offset setting via app or uConfig |
Power supply | 15..35 V = SELV |
Power consumption | max. 2,5 W (24 V =), 4,3 VA (24 V ~) |
Material in touch with media | Sensor probe, brass, spring loaded sensor |
Display | LCD 29x35 mm, RGB backlight, with traffic light function, threshold values configurable, optionally configurable via app or uConfig |
Enclosure | USE-M, impact- and shock-resistant enclosure with quick-release cover, PC |
Colour | pure white, transparent cover |
Protection (IP) | IP65, according to EN 60529 |
Connection | removable cable entry flextherm M20 for wire Ø=4,5..9 mm, removable plug-in terminal, max. 2,5 mm² |
Mounting | along the pipe or sideways |
Packaging length (mm) | 128 |
Packaging width (mm) | 100 |
Packaging height (mm) | 65 |
Packaging | case packaging |
Device length (mm) | 85 |
Device width (mm) | 84 |
Device height (mm) | 56 |
Accessories
Item No.: 668071
3.20 EUR