NOVOS 7 move
NOVOS 7 move AP CO2 temp_rH white
CO2 Traffic Light, Room sensor temperature, relative humidity, CO2 | 0..+50 °C
0..100% rH non-condensing
0..5000 ppm
Application/type | CO2 Traffic Light, Room sensor |
---|---|
Purpose | Measure values |
Measured values | temperature, relative humidity, CO2 |
Operating elements | 4 favourite buttons |
Configuration | NOVOSapp, uConfig |
Operating range temperature (°C) | 0..+50 |
Operating ranges temperature (°C) | 0..+50 |
Operating range humidity | max. 85% rH non-condensing |
Accuracy temperature | ±0,5 K (typ. at 21 °C) |
Measuring range humidity | 0..100% rH non-condensing |
Accuracy humidity | ±2% between 10..90% rH (typ. at 21 °C) |
Measuring range CO2 | 0..5000 ppm |
Accuracy CO2 | ±50 ppm +3% of measured value (typ. at 21 °C, 50% rH, 1015 hPa), self-calibration Dual Channel |
Power supply | 15..35 V = SELV, 19..29 V ~ SELV |
Display | TFT 3,5", 320x480 px, with traffic light function, threshold values configurable, optionally configurable via app or uConfig |
Enclosure | NOVOS 5, PC V0 |
Colour | pure white |
Protection (IP) | IP30, according to EN 60529 |
Connection | tool-free mountable spring clamp, max. 1,5 mm², cable entry via rear opening, predetermined breaking point (bottom) or drilling mark (top) |
Mounting | flush-mounted on standard EU box (Ø=60 mm), surface-mounted flat on base using adhesive foil or screws, base part can be mounted and wired separately |
Packaging length (mm) | 110 |
Packaging width (mm) | 158 |
Packaging height (mm) | 232 |
Device length (mm) | 95 |
Device width (mm) | 105 |
Device height (mm) | 165 |