Thermokon
430.50 EUR
Item No.: 826211
Group: AQ2
Add to comparison list Add to project Show accessories

NOVOS 3

NOVOS 3 CO2+VOC temp_rH white EPD RS485 Modbus

Room sensor temperature, relative humidity, CO2, VOC | RS485 Modbus | 0..+50 °C
0..100% rH non-condensing, 0..85 KJ/kg enthalpy, 0..50 | 0..80 g/m³ absolute humidity, 0..+50 | -20..+80 °C dew point, optionally configurable
0..2000 ppm, 0..5000 ppm, optionally configurable

Application/type Room sensor
Purpose Measure values
Measured values temperature, relative humidity, CO2, VOC
Interface RS485 Modbus
Configuration NOVOSapp, uConfig, BUS, jumper, each output can be set to get a variable mix of CO2 and VOC by configuration via app or uConfig, (depending on type)
Input 1x input for floating contact
Network technology RS485 Modbus
Operating range temperature (°C) 0..+50
Operating ranges temperature (°C) 0..+50
Output signal temperature 0..+50 °C (default setting), selectable from 4 temperature ranges -40..+60 | 0..+50 | -20..+80 | -15..+35 °C -50..+50 | 0..+50 | -20..+80 | -15..+35 °C, optionally configurable
Operating range humidity max. 85% rH non-condensing
Accuracy temperature ±0,5 K (typ. at 21 °C)
Measuring range humidity 0..100% rH non-condensing, 0..85 KJ/kg enthalpy, 0..50 | 0..80 g/m³ absolute humidity, 0..+50 | -20..+80 °C dew point, optionally configurable
Accuracy humidity ±2% between 10..90% rH (typ. at 21 °C)
Measuring range CO2 0..2000 ppm, 0..5000 ppm, optionally configurable
Accuracy CO2 ±50 ppm +3% of measured value (typ. at 21 °C, 50% rH, 1015 hPa), self-calibration Dual Channel
Measuring VOC (mixed gas) heated metal oxide semiconductor
Power supply 15..35 V = SELV, 19..29 V ~ SELV
Power consumption typ. 0,4 W (24 V =), 0,8 VA (24 V ~)
Display ePaper Display 44x24 mm
Enclosure PC V0
Colour pure white
Protection (IP) IP20, according to EN 60529
Connection tool-free mountable spring clamp, max. 1,5 mm², cable entry via rear opening, predetermined breaking point (bottom) or drilling mark (top)
Mounting flush-mounted on standard EU box (Ø=60 mm), surface-mounted flat on base using adhesive foil or screws, base part can be mounted and wired separately
Packaging length (mm) 115
Packaging width (mm) 105
Packaging height (mm) 30
Packaging case packaging
Device length (mm) 110
Device width (mm) 100
Device height (mm) 23
Notes mixed gas sensors detect gases and vapours which can be oxidised (burnt): Body odours, tobacco smoke, exhalations emitted by materials (furniture, carpets, paint, glue ...)
430.50 EUR
Item No.: 826211
Group: AQ2
Add to comparison list Add to project Show accessories
Top