LCR Touch
LCR Touch white temp RS485 Modbus
Room operating unit temperature | RS485 Modbus | Room Climate Control, Lighting control, Shading control, Measure values
Application/type | Room operating unit |
---|---|
Purpose | Room Climate Control, Lighting control, Shading control, Measure values |
Measured values | temperature |
Interface | RS485 Modbus |
Functions | temperature control, fan control, lighting, blinds/shutter, night setback |
Operating functions | setpoint adjustment 0..+50 °C, +16..+30 °C (default setting), optionally configurable, fan stage adjustment, light ON/OFF/DIM, blind UP/DOWN, ECO function, status displays |
Operating elements | 5 touch buttons |
Input | 1x input for change-over sensor NTC10k, 2x input digital for floating contact, 1x ESI for window contact, dew point, 1x OCC for presence detection, key card switch |
Network technology | RS485 Modbus |
Data transmission | RTU, half-duplex, baud rate 4.800, 9.600, 19.200 or 38.400, parity: none (2 stop bits), even or odd (1 stop bit) |
Operating range temperature (°C) | -10..+50 |
Operating ranges temperature (°C) | -10..+50 |
Operating range humidity | max. 85% rH short term condensation |
Accuracy temperature | ±1 K (typ. at 21 °C) |
Power supply | 24 V = (±20%) SELV, 24 V ~ (±20%) SELV |
Power consumption | typ. 0,3 W (24 V =), 5 VA (24 V ~) |
Display | LCD 64x41 mm, backlight white |
Enclosure | ABS |
Colour | pure white, frame silver |
Protection (IP) | IP20, according to EN 60529 |
Connection | terminal block, max. 1,5 mm², cable entry via rear opening |
Mounting | flush-mounted in standard EU box (Ø=60 mm) |
Packaging | case packaging |
Device length (mm) | 86 |
Device width (mm) | 86 |
Device height (mm) | 41 |