Thermokon
231.50 EUR
Item No.: 817707
Group: R1
Add to comparison list Add to project Show accessories

LCF02 QTouch

LCF02 QTouch rH AO5DO RS485 Modbus black

Fan coil thermostat, Room controller temperature, humidity | RS485 Modbus, 0..10 V, Switch contact | Room Climate Control, Measure values
0..10 V, min. load 10 kΩ, to control EC fan, heating + cooling or to control 6-way control valve 2x contact NO, 1x heating, 1x cooling, 3x contact NO, fan stages, load max. 3 A, max. 250 V ~

Application/type Fan coil thermostat, Room controller
Purpose Room Climate Control, Measure values
Sensor elements temperature, humidity
Measured values temperature, relative humidity
Interface RS485 Modbus, 0..10 V, Switch contact
On stock No
Functions fan control relay, fan control 0..10 V, heating + cooling relay, heating + cooling 0..10 V, heating relay, to control 6-way control valve, cooling relay, change-over, integrated PI and two-/three-position controller, frost protection, window/door monitoring, presence
Operating functions setpoint adjustment temperature, +16..+30 °C (default setting), optionally configurable, fan stage adjustment, status displays
Operating elements 6 capacitive buttons
Configuration BUS
Output voltage 0..10 V, min. load 10 kΩ, to control EC fan, heating + cooling or to control 6-way control valve
Output switch contact 2x contact NO, 1x heating, 1x cooling, 3x contact NO, fan stages, load max. 3 A, max. 250 V ~
Input 1x input for additional external NTC10k, 1x ESI for window contact, dew point, 1x OCC for presence detection, key card switch
Network technology RS485 Modbus
Data transmission RTU, half-duplex, baud rate 4.800, 9.600, 19.200 or 38.400, parity: none (2 stop bits), even or odd (1 stop bit)
Operating range temperature (°C) -10..+50
Operating range humidity max. 85% rH non-condensing
Accuracy temperature ±1 K (typ. at 21 °C)
Power supply 100..240 V ~
Power consumption max. 5 VA (230 V ~)
Display LCD 102x56 mm, backlight black
Enclosure ABS, glass
Colour black
Protection (IP) IP20, according to EN 60529
Connection terminal block, max. 1,5 mm²
Mounting flush-mounted in standard EU box (Ø=60 mm, depth min. 45 mm)
Packaging case packaging
Device length (mm) 86
Device width (mm) 86
Device height (mm) 45
Gefahrgut No
231.50 EUR
Item No.: 817707
Group: R1
Add to comparison list Add to project Show accessories
Top