Thermokon
423.30 EUR
Item No.: 751650
Group: AQ1
Add to comparison list Add to project Show accessories

LA+

LA+ CO2+VOC temp 3xV

Outdoor sensor temperature, CO2, VOC, CO2/VOC mix | 0..+50 °C
Active, 0..5 V, 0..10 V | IP65 according to EN 60529

Application/type Outdoor sensor
Purpose Measure values
Measured values temperature, CO2, VOC, CO2/VOC mix
Interface Active, 0..5 V, 0..10 V
Configuration USEapp, uConfig, jumper, each output can be set to get a variable mix of CO2 and VOC by configuration via app or uConfig
Sensor NDIR (non-dispersive, infrared)
Output voltage 3x 0..10 V or 0..5 V, adjustable via jumper, live-zero configuration via app or uConfig, min. load 10 kΩ
Operating range temperature (°C) 0..+50
Operating ranges temperature (°C) 0..+50
Operating range humidity max. 85% rH short term condensation
Measuring range CO2 0..2000 ppm, 0..5000 ppm, optionally configurable
Accuracy CO2 ±50 ppm +3% of measured value (typ. at 21 °C, 50% rH, 1015 hPa), self-calibration Dual Channel
Measuring VOC (mixed gas) heated metal oxide semiconductor, self-calibration
Power supply 15..35 V = SELV, 19..29 V ~ SELV
Power consumption max. 2,5 W (24 V =), 4,3 VA (24 V ~)
Enclosure USE-M, impact- and shock-resistant enclosure with quick-release cover, PC
Colour pure white
Protection (IP) IP65, according to EN 60529
Connection removable cable entry flextherm M20 for wire Ø=4,5..9 mm, removable plug-in terminal, max. 2,5 mm²
Delivery content incl. mounting base enclosure USE-M pure white, incl. mounting set (screws and accessories)
Packaging length (mm) 128
Packaging width (mm) 100
Packaging height (mm) 65
Packaging case packaging
Device length (mm) 85
Device width (mm) 93
Device height (mm) 45
Notes mixed gas sensors detect gases and vapours which can be oxidised (burnt): Body odours, tobacco smoke, exhalations emitted by materials (furniture, carpets, paint, glue ...)
Option enclosure LCD 29x35 mm, RGB backlight
423.30 EUR
Item No.: 751650
Group: AQ1
Add to comparison list Add to project Show accessories
Top