JOY Fancoil
JOY Fancoil EC AO2DO temp RS485 Modbus white
Fan coil thermostat, Room controller temperature | RS485 Modbus, 0..10 V, Switch contact | Room Climate Control, Measure values
0..10 V, max. load 5 mA, to control EC fan 2x contact NO, 1x heating, 1x cooling, load max. 500 mA (240 V, Triac)
| Application/type | Fan coil thermostat, Room controller |
|---|---|
| Purpose | Room Climate Control, Measure values |
| Sensor elements | temperature |
| Measured values | temperature |
| Interface | RS485 Modbus, 0..10 V, Switch contact |
| On stock | Yes |
| Functions | fan control 0..10 V, heating + cooling relay, change-over, integrated PI and two-/three-position controller, frost protection, window/door monitoring, presence |
| Operating functions | setpoint adjustment temperature, fan stage adjustment, standby/presence detection |
| Operating elements | 5 capacitive buttons |
| Configuration | uConfig, BUS |
| Output voltage | 0..10 V, max. load 5 mA, to control EC fan |
| Output switch contact | 2x contact NO, 1x heating, 1x cooling, load max. 500 mA (240 V, Triac) |
| Input | 1x input for NTC10k or floating contact, 1x input for potential contact (230 V ~), 1x input for floating contact |
| Network technology | RS485 Modbus |
| Data transmission | RTU, half-duplex, baud rate 9.600, 19.200, 38.400 or 57.600, parity: none (2 stop bits), even or odd (1 stop bit) |
| Operating range temperature (°C) | 0..+50 |
| Operating ranges temperature (°C) | 0..+50 |
| Output signal temperature | 0..+50 °C |
| Operating range humidity | max. 85% rH non-condensing |
| Accuracy temperature | ±1 K (typ. at 21 °C), within default measuring range |
| Measuring range CO2 | 0..2000 ppm |
| Accuracy CO2 | ±50 ppm +5% of measured value (typ. at 21 °C, 50% rH, 1015 hPa) |
| Power supply | 85..260 V ~ |
| Power consumption | max. 3 VA (260 V ~) |
| Display | LCD 60x44 mm, 240x160 px, backlight cold white |
| Enclosure | PC, cover glass |
| Colour | pure white |
| Protection (IP) | IP30, according to EN 60529 |
| Connection | terminal block, max. 1,5 mm², inputs max. 1,0 mm² |
| Mounting | in standard EU box (Ø=60 mm, depth min. 45 mm) |
| Packaging length (mm) | 196 |
| Packaging width (mm) | 162 |
| Packaging height (mm) | 37 |
| Device length (mm) | 140 |
| Device width (mm) | 78 |
| Device height (mm) | 35 |
| Weight (g) | 195 |
| Gefahrgut | No |