FTK+
FTK+ 140 Basic RS485 Modbus
Duct sensor temperature, relative humidity
RS485 Modbus | IP65 according to EN 60529
Pipe, PA6, with filter stainless steel wire mesh, black, Ø=19,5 mm, 140 mm
Application/type | Duct sensor |
---|---|
Purpose | Measure values |
Measured values | temperature, relative humidity |
Interface | RS485 Modbus |
Configuration | BUS, DIP switches |
Network technology | RS485 Modbus |
Operating range temperature (°C) | -20..+70 |
Operating ranges temperature (°C) | -20..+70 |
Operating range humidity | max. 85% rH short term condensation |
Accuracy temperature | ±0,3 K (typ. at 21 °C), within default measuring range |
Measuring range humidity | 0..100% rH non-condensing |
Accuracy humidity | ±2% between 10..90% rH (typ. at 21 °C) |
Power supply | 15..24 V = (±10%) SELV, 24 V ~ (±10%) SELV |
Power consumption | max. 0,7 W (24 V =), 1,8 VA (24 V ~) |
Material in touch with media | Pipe, PA6, with filter stainless steel wire mesh, black, Ø=19,5 mm |
Installation length (mm) | 140 |
Enclosure | USE-S, impact- and shock-resistant enclosure with quick-release cover, PC |
Colour | pure white |
Protection (IP) | IP65, according to EN 60529 |
Connection | removable cable entry flextherm M20 for wire Ø=4,5..9 mm, removable plug-in terminal, max. 2,5 mm² |
Delivery content | incl. mounting flange, incl. mounting set (screws and accessories) |
Packaging length (mm) | 70 |
Packaging width (mm) | 70 |
Packaging height (mm) | 200 |
Packaging | case packaging |
Device length (mm) | 63 |
Device width (mm) | 68 |
Device height (mm) | 180 |
Notes | air speed max. 12 m/s |