DPL02
DPL02 6 A HS G1/4“
Differential pressure transducer max. 16 bar, fluids
differential pressure 0..6 bar | Active, 4..20 mA | IP65 according to EN 60529
| Application/type | Differential pressure transducer |
|---|---|
| Purpose | Measure values |
| Sensor elements | differential pressure |
| Measured values | differential pressure |
| Interface | Active, 4..20 mA |
| On stock | No |
| Output current | 4..20 mA, max. load 850 Ω |
| Operating range temperature (°C) | -30..+80 |
| Operating ranges temperature (°C) | -30..+80 |
| Operating range humidity | max. 85% rH short term condensation |
| Operating range pressure | max. 16 bar, fluids |
| Measuring range pressure | 0..6 bar |
| Accuracy pressure | ±1% of measuring range (typ. at -5..+75 °C) |
| Power supply | 15..24 V = (±10%) SELV |
| Power consumption | max. 0,5 W (24 V =) |
| Material in touch with media | stainless steel, G1/4" |
| Enclosure | stainless steel V2A (1.4305) |
| Protection (IP) | IP65, according to EN 60529 |
| Connection | angle plug DIN 43650, type A |
| Packaging length (mm) | 170 |
| Packaging width (mm) | 120 |
| Device length (mm) | 58 |
| Device width (mm) | 40 |
| Device height (mm) | 150 |
| Weight (g) | 580 |
| Catalogue table | Differential pressure transducer |
| Gefahrgut | No |