Filter







Reset
Show item

Cable Sensors

TF14

Cable sensor for temperature measurement in HVAC applications. Depending on the application requirements, different PVC, silicone and PTFE cables are available. The TF14 with its 4 mm diameter pocket is well suited for fast response applications.

Application/type Cable sensor
Purpose Measure values
Measured values temperature
Interface Passive
Sensor SI-Protection against permeation of humidity and mechanical stress (e.g. vibration), PT1000 DIN cl. B, PT100 DIN cl. B, PT1000 1/3 DIN, PT100 1/3 DIN, Ni1000 DIN cl. B, Ni1000TK5000, NTC10k, NTC10k Precon, NTC10K Carel, NTC20K, NTC1,8K, NTC5K, passive
Operating range temperature (°C) -80..+250
Operating ranges temperature (°C) -35..+100, -50..+150, -50..+180, -80..+250
Accuracy temperature ±0,1 K (typ. at 0 °C), ±0,3 K (typ. at 0 °C), ±0,4 K (typ. at 0 °C), ±0,2 K (typ. at 25 °C), ±0,22 K (typ. at 25 °C), ±0,26 K (typ. at 25 °C), see characteristic curve
Material in touch with media Sensor probe, Ø=4 mm, stainless steel V4A (1.4571), 16-point pressed (IP65), rolled (IP67)
Installation length (mm) 50, 100, 150
Protection (IP) IP65, IP67, enclosure IP65, according to EN 60529
Connection cable PVC, silicone, PTFE, 0,14 mm², 2-wire, 3-wire, 4-wire
Length connection wire (m) 1, 2, 4, 6
Comparison list