Application/type | Pendulum sensor, Room sensor |
---|---|
Purpose | Measure values |
Measured values | temperature |
Interface | RS485 BACnet, Passive, Active, 0..5 V, 0..10 V, 4..20 mA |
Configuration | USEapp, uConfig, BUS, jumper |
Sensor | SI-Protection against permeation of humidity and mechanical stress (e.g. vibration) |
Output voltage | 0..10 V or 0..5 V, min. load 5 kΩ |
Output current | 4..20 mA, max. load 500 Ω |
Output switch contact | 2x floating contact NO for 24 V ~ or 24 V = / 3 A |
Network technology | RS485 Modbus, RS485 BACnet (MS/TP), LON FT (free topology) |
Data transmission | RTU, half-duplex, baud rate 9.600, 19.200, 38.400 or 57.600, parity: none (2 stop bits), even or odd (1 stop bit) |
Operating range temperature (°C) | -35..+70 |
Output signal temperature | scaling analogue output, 0..+160 °C (default setting), -20..+80 °C (default setting), selectable from 4 temperature ranges -50..+50 | -20..+80 | -15..+35 | -10..+120 | 0..+50 | 0..+100 | 0..+160 | 0..+250 °C, adjustable at the transducer, optionally configurable via app or uConfig, depending on used sensor |
Operating range humidity | max. 85% rH short term condensation |
Accuracy temperature | ±0,3 K (typ. at 21 °C), ±0,5 K (typ. at 21 °C), within default measuring range, depending on length of connection wire and sensor |
Power supply | 15..24 V = (±10%) SELV, 15..35 V = SELV, 24 V ~ (±10%) SELV, 19..29 V ~ SELV |
Power consumption | typ. 0,4 W (24 V =), typ. 0,5 W (24 V =), typ. 2,5 W (24 V =), 0,8 VA (24 V ~), 4,3 VA (24 V ~) |
Material in touch with media | Sensor probe, Ø=15 mm, stainless steel V2A (1.4305), length 100 mm, hex pressed (IP65) |
Display | LCD 29x35 mm, RGB backlight, with traffic light function, threshold values configurable, optionally configurable via app or uConfig |
Enclosure | USE-S, impact- and shock-resistant enclosure with quick-release cover, PC, USE-M, impact- and shock-resistant enclosure with quick-release cover, PC |
Colour | pure white |
Protection (IP) | IP65, according to EN 60529 |
Connection | removable cable entry flextherm M20 for wire Ø=4,5..9 mm, removable cable entry M25 with fourfold cable entry for wire with max. Ø=7 mm, removable plug-in terminal, max. 2,5 mm², BUS max. 1,5 mm², relay max. 1,5 mm² |
Connection cable | PVC, 0,25 mm², white |
Length connection wire (m) | 1, 2, 4, 6 |
Delivery content | incl. mounting base enclosure USE-S pure white, incl. mounting base enclosure USE-M pure white, incl. mounting set (screws and accessories) |
Packaging length (mm) | 200 |
Packaging width (mm) | 130 |
Device length (mm) | 63 |
Device width (mm) | 68 |
Device height (mm) | 40 |
Gefahrgut | No |