| Application/type |
Cable sensor, Surface sensor |
| Purpose |
Measure values |
| Measured values |
temperature |
| Interface |
Passive |
| On stock |
No |
| Sensor |
SI-Protection against permeation of humidity and mechanical stress (e.g. vibration), Pt1000 DIN cl. B, Pt100 DIN cl. B, Pt1000 1/3 DIN, Pt100 1/3 DIN, Ni1000 DIN cl. B, Ni1000TK5000, NTC10k, NTC10k Precon, NTC20k, NTC1,8k, NTC5k, LM235Z, KTY81-110, KTY81-121, KTY81-210, passive |
| Operating range temperature (°C) |
-50..+180 |
| Operating ranges temperature (°C) |
-35..+100, -50..+150, -50..+180 |
| Operating range humidity |
max. 85% rH short term condensation |
| Accuracy temperature |
±0,1 K (typ. at 0 °C), ±0,3 K (typ. at 0 °C), ±0,4 K (typ. at 0 °C), ±0,2 K (typ. at 25 °C), ±0,2 K (typ. at 25 °C, temperature dependend), see characteristic curve |
| Material in touch with media |
Sensor probe, Ø=11/15 mm, aluminium, hex pressed (IP65) |
| Installation length (mm) |
28 |
| Enclosure |
USE-S, impact- and shock-resistant enclosure with quick-release cover, PC |
| Colour |
pure white |
| Protection (IP) |
IP65, according to EN 60529 |
| Connection |
removable cable entry flextherm M20 for wire Ø=4,5..9 mm, removable plug-in terminal, max. 2,5 mm² |
| Connection cable |
PVC, silicone, 0,25 mm², 2-wire, 3-wire, 4-wire |
| Length connection wire (m) |
1, 2, 4, 6 |
| Delivery content |
incl. mounting base enclosure USE-S pure white, incl. fixing kit rawlplugs and screws (2x each) |
| Gefahrgut |