Room Sensors
NOVOS 5
Active room sensor in the NOVOS 5 enclosure for measurement of temperature, humidity (relative and absolute humidity, enthalpy, dew point), CO2 and mixed gas (VOC) depending on the variant. The maintenance-free sensor contributes to a pleasant room climate and well-being. Typical applications include schools, office buildings, hotels or cinemas. The NOVOS 5 uses an LCD with color-changing backlight for displaying the measured values and exceeding threshold values. Different parameters like the display settings can be individually configured via Thermokon NOVOSapp. Optionally, operating elements for controlling HVAC systems can be added (see product NOVOS 5 x in the chapter 'Room Operating Units').
Application/type | CO2 Traffic Light, Room sensor |
---|---|
Purpose | Measure values |
Measured values | temperature, relative humidity, absolute humidity, enthalpy, dew point, CO2, VOC, CO2/VOC mix |
Interface | RS485 Modbus, RS485 BACnet, Active, 0..5 V, 0..10 V, 4..20 mA |
Configuration | NOVOSapp, uConfig, BUS, ETS (KNX), (depending on type) |
Output voltage | 0..10 V or 0..5 V, 2x 0..10 V or 0..5 V, 3x 0..10 V or 0..5 V, 4x 0..10 V or 0..5 V, adjustable via jumper, live-zero configuration via app or uConfig, min. load 10 kΩ |
Output current | 4..20 mA, 2x 4..20 mA, 3x 4..20 mA, 4x 4..20 mA, max. load 500 Ω |
Input | 1x input for NTC10k or floating contact, 1x input for floating contact, 2x input for floating contact |
Network technology | RS485 Modbus, RS485 BACnet (MS/TP), KNX (TP1) |
Data transmission | RTU, half-duplex, baud rate 9.600, 19.200, 38.400 or 57.600, parity: none (2 stop bits), even or odd (1 stop bit) |
Operating range temperature (°C) | 0..+50 |
Output signal temperature | 0..+50 °C (default setting), selectable from 4 temperature ranges -40..+60 | 0..+50 | -20..+80 | -15..+35 °C -50..+50 | 0..+50 | -20..+80 | -15..+35 °C, optionally configurable |
Operating range humidity | max. 85% rH non-condensing |
Accuracy temperature | ±0,5 K (typ. at 21 °C) |
Measuring range humidity | 0..100% rH non-condensing, 0..85 KJ/kg enthalpy, 0..50 | 0..80 g/m³ absolute humidity, 0..+50 | -20..+80 °C dew point, optionally configurable |
Accuracy humidity | ±2% between 10..90% rH (typ. at 21 °C) |
Measuring range CO2 | 0..2000 ppm, 0..5000 ppm, optionally configurable |
Accuracy CO2 | ±50 ppm +3% of measured value (typ. at 21 °C, 50% rH, 1015 hPa), self-calibration Dual Channel |
Measuring VOC (mixed gas) | heated metal oxide semiconductor |
Power supply | 24 V = (±10%) SELV, 15..35 V = SELV, 19..29 V ~ SELV, mains adapter 100..230 V (50/60 Hz), max. 0,4A, Flush-mounted power supply 230 V (±10%, 50/60 Hz), max. 0.4 A |
Power consumption | typ. 0,4 W (24 V =), 0,8 VA (24 V ~), max. 0,5 W (24 V =) |
Display | LCD 29x35 mm, RGB backlight, with traffic light function, threshold values configurable, optionally configurable via app or uConfig |
Enclosure | PC V0 |
Colour | pure white, aluminium, black |
Protection (IP) | IP30, according to EN 60529 |
Connection | tool-free mountable spring clamp, max. 1,5 mm², removable plug-in terminal, max. Ø=0,8 mm, cable entry via rear opening, predetermined breaking point (bottom) or drilling mark (top) |
Mounting | flush-mounted on standard EU box (Ø=60 mm), flush-mounted in standard EU box (Ø=60 mm, depth min. 45 mm), surface-mounted flat on base using adhesive foil or screws, base part can be mounted and wired separately |
Delivery content | incl. stand and power supply unit |
Packaging length (mm) | 170 |
Packaging width (mm) | 110 |
Packaging height (mm) | 45 |
Device length (mm) | 163 |
Device width (mm) | 106 |
Device height (mm) | 25 |
Notes | mixed gas sensors detect gases and vapours which can be oxidised (burnt): Body odours, tobacco smoke, exhalations emitted by materials (furniture, carpets, paint, glue ...) |