Application/type |
Room controller |
Purpose |
Room Climate Control, Measure values |
Measured values |
temperature |
Interface |
LON FT, Active, 0..10 V |
Functions |
presence |
Operating functions |
presence detection, status feedback via LED |
Operating elements |
button (T) |
Output voltage |
2x 0..10 V, min. load 10 kΩ, heating + cooling or to control 6-way control valve |
Input |
2x input digital for floating switch contact, 4x input digital for floating switch contact |
Network technology |
LON FT (free topology) |
Operating range temperature (°C) |
-35..+70 |
Operating ranges temperature (°C) |
-35..+70 |
Operating range humidity |
max. 85% rH non-condensing |
Accuracy temperature |
±0,5 K (typ. at 21 °C) |
Power supply |
24 V = (±10%) SELV, 24 V ~ (±10%) SELV |
Power consumption |
typ. 0,9 W (24 V =), 1 VA (24 V ~) |
Display |
LED for status feedback, green |
Enclosure |
central disc in design of the manufacturer, (varies depending on switch range) |
Protection (IP) |
IP20, according to EN 60529 |
Connection |
terminal block, max. 1,5 mm², pluggable |
Switch ranges |
Feller, Gira |
Switch range Feller |
EDIZIOdue |
Switch range Gira |
E2 |
Mounting |
flush-mounted in standard EU box (Ø=60 mm, depth min. 45 mm) |
Delivery content |
incl. frame |
Packaging length (mm) |
90 |
Packaging width (mm) |
90 |
Packaging height (mm) |
80 |
Packaging |
case packaging |
Device length (mm) |
81 |
Device width (mm) |
81 |
Device height (mm) |
38 |