Filter
Show item AF25+ RS485 BACnet
Contact sensor in the USE enclosure with connection cable and brass lug for surface temperature measurement (cold or hot water) on pipes and other curved surfaces.
Contact sensor in the USE enclosure with connection cable and brass lug for surface temperature measurement (cold or hot water) on pipes and other curved surfaces.
Application/type | Contact sensor, Cable sensor |
---|---|
Purpose | Measure values |
Measured values | temperature |
Interface | RS485 BACnet, Active, 0..5 V, 0..10 V |
Configuration | USEapp, uConfig, BUS |
Sensor | SI-Protection against permeation of humidity and mechanical stress (e.g. vibration) |
Output voltage | 0..10 V or 0..5 V, adjustable via jumper, live-zero configuration via app or uConfig, min. load 10 kΩ |
Network technology | RS485 BACnet (MS/TP) |
Operating range temperature (°C) | -50..+135 |
Operating ranges temperature (°C) | -50..+135 |
Output signal temperature | scaling analogue output, 0..+160 °C (default setting), selectable from 4 temperature ranges -50..+50 | -20..+80 | -15..+35 | -10..+120 | 0..+50 | 0..+100 | 0..+160 | 0..+250 °C, optionally configurable |
Operating range humidity | max. 85% rH short term condensation |
Accuracy temperature | ±0,5 K (typ. at 21 °C), within default measuring range, offset setting via app or uConfig |
Power supply | 15..35 V = SELV, 19..29 V ~ SELV |
Power consumption | max. 2,5 W (24 V =), 4,3 VA (24 V ~) |
Material in touch with media | Sensor probe, Ø=6 mm, brass, with contact tongue, 16-point pressed (IP65) |
Installation length (mm) | 35 |
Enclosure | USE-M, impact- and shock-resistant enclosure with quick-release cover, PC |
Colour | pure white |
Protection (IP) | IP65, according to EN 60529 |
Connection | removable cable entry M25 with fourfold cable entry for wire with max. Ø=7 mm, removable plug-in terminal, max. 2,5 mm², BUS max. 1,5 mm² |
Connection cable | PVC, 0,25 mm² |
Length connection wire (m) | 2 |
Delivery content | incl. mounting base enclosure USE-M pure white, incl. mounting set (screws and accessories) |
Packaging | case packaging |