TS3 3-phase

Power thyristors are used as actuators for industrial power controls (e.g. fans, pumps, lamps, heating registers, industrial furnaces). Their solid and compact construction ensures reliable control and and high efficiency.

Output voltage reference voltage for potentiometer: 10 V =
Output switch contact signal contact in case of fault state, changeover contact floating for 230 V ~ / 2 A, signal contact at 100% Ua, changeover contact floating for 230 V ~ / 2 A, operation signal, changeover contact floating for 230 V ~ / 2 A, output for ohmic and inductive loads: 15 A: 10 kW (400 V ~ / 15 A) | 25 A: 16 kW (400 V ~ / 25 A) | 35 A: 23 kW (400 V ~ / 35 A) | 50 A: 33 kW (400 V ~ / 50 A)
Power supply L1, L2, L3: 400 V ~ 45..65 Hz self-synchronizing
Inputs electrical activation via set point signal 0..10 V = or 0..20 mA (selectable via DIP switches), input for potentiometer 2,5..10 kΩ, PWM input 5 V / 5..10 kHz, input for PTC according to DIN 44081, input for reset
Functions phase angel, optional oscillation, start-up period adjustable (0..10 sec.)
Display 4 LEDs for showing state of device
Enclosure aluminium
Protection IP40 according to EN 60529
Connection electrical terminal block, max. 1,5..10 mm² (depending on type)
Ambient condition 0..+50 °C
Mounting 4 mounting holes Ø=8 mm for mounting on galvanized mounting plates (control cabinet)