The TS2 three-phase power thyristor controller is used to control the load or power of industrial load applications (e.g. fans, pumps, lamps, heating coils, industrial ovens). Its solid and compact design permit seamless installation and a wear-free control with a high degree of efficiency.

Output voltagereference voltage for potentiometer: 10 V =
Output switch contactsignal contact in case of fault state, changeover contact floating for 230 V ~ / 2 A, signal contact at 100% Ua, changeover contact floating for 230 V ~ / 2 A, operation signal, changeover contact floating for 230 V ~ / 2 A, output for ohmic and inductive loads: 75 A: 50 kW (400 V ~ / 75 A) | 90 A: 60 kW (400 V ~ / 90 A) | 120 A: 78 kW (400 V ~ / 120 A)
Power supplyL1, L2, L3: 400 V ~ (± 15%) 48..62 Hz self-synchronizing
Inputselectrical activation via setpoint signal 0..10 V =, 0..20 mA or 4..20 mA (selectable via DIP switches), input for potentiometer 2,5..10 kΩ, input for PTC according to DIN 44081
Functionsphase angel, optional oscillation
Display9 LEDs for showing state of device
Enclosurealuminium with plexiglas cover
Protection (IP)IP23 according to DIN EN 60529
Electrical connectionPower connections, M8 connection screw for cable lug, connection control electronics, max. 1.5 mm²
Ambient condition0..+55 °C
Mounting4 mounting holes Ø=8 mm for mounting on galvanized mounting plates (control cabinet)