The TS3 single-phase power thyristor controller is used to control the load or power of industrial load applications (e.g. fans, pumps, lamps, heating coils, industrial ovens). Its solid and compact design permit seamless installation and a wear-free control with a high degree of efficiency.
Output voltage | reference voltage for potentiometer: 10 V = |
---|---|
Output switch contact | signal contact in case of fault state, floating contact NO for 230 V ~ / 2 A, output for ohmic and inductive loads: 15 A: 3,5 kW (230 V ~ / 15 A) | 25 A: 5,75 kW (230 V ~ / 25 A) | 35 A: 8,05 kW (230 V ~ / 35 A) | 50 A: 11,5 kW (230 V ~ / 50 A) |
Power supply | L1, N: 230 V ~ 45..65 Hz self-synchronizing |
Inputs | electrical activation via setpoint signal 0..10 V =, 0..20 mA or 4..20 mA (selectable via DIP switches), input for potentiometer 2,5..10 kΩ |
Functions | phase angel, optional oscillation |
Display | 4 LEDs for showing state of device |
Enclosure | aluminium |
Protection (IP) | IP40 according to EN 60529 |
Electrical connection | screw terminal, max. 1,5..10 mm² (depending on type) |
Ambient condition | 0..+50 °C |
Mounting | prepared for mounting on DIN rail TS35 (35x7,5 mm) according to EN 60715 |