TS1 1-phase

The TS1 single-phase power thyristor controller is used to control the load or power of industrial load applications (e.g. fans, pumps, lamps, heating coils, industrial ovens). Its solid and compact design permit seamless installation and a wear-free control with a high degree of efficiency.

Output voltagereference voltage for potentiometer: 10 V =
Output switch contactsignal contact at 100% Ua, floating contact NO for 250 V ~ / 3 A or 24 V = / 3 A, output for ohmic and inductive loads: 2 A: 0,46 kW (230 V ~ / 2 A) | 4 A: 0,92 kW (230 V ~ / 4 A) | 6 A: 1,38 kW (230 V ~ / 6 A) | 8 A: 1,84 kW (230 V ~ / 8 A) | 10 A: 2,3 kW (230 V ~ / 10 A) | 12 A: 2,76 kW (230 V ~ / 12 A)
Power supplyL1, N: 230 V ~ 48..62 Hz self-synchronizing
Power consumption2 A: typ. 2,5 W | 4 A: typ. 4,5 W | 6 A: typ. 6,5 W | 8 A: typ. 9,0 W | 10 A: typ. 11,0 W | 12 A: typ 13,0 W (230 V ~)
Inputselectrical activation via setpoint signal 0..10 V = or 0..20 mA (selectable via DIP switches), input for potentiometer 2,5..10 kΩ
Functionsphase angel, optional oscillation
DisplayLED – power supply OK, LED – modulation amplitude 100%
EnclosurePA
Protection (IP)IP40 according to EN 60529, screw terminals IP23 according to DIN EN 60529
Electrical connectionterminal block, max. 2,5 mm²
Ambient condition0..+45 °C
Mountingprepared for mounting on DIN rail TS35 (35x7,5 mm) according to EN 60715
Notesversions up to 4 A with heat sink, version 6 A with heat sink, versions 8 A and higher with heat sink and fan
Contact

Contact us:


Thermokon Sensortechnik GmbH
Platanenweg 1
35756 Mittenaar
Tel.: +49 2778 6960-0


Write email