WRF06 BUS

Flush mounted sensor for measuring temperature in room and office applications. Designed for control and monitoring systems.

Measuring values temperature
Output voltage AO2V: 2x 0..10 V
Network technology BACnet MS/TP, LON FT (free topology), RS485 Modbus
Power supply 15..24 V = (±10%) or 24 V ~ (±10%) SELV
Power consumption typ. 0,9 W (24 V =) | 1 VA (24 V ~), LON: typ. 0,7 W (24 V =) | 2,5 VA (24 V ~)
Measuring range temp. 0..+50 °C
Operating temperature range permissible working temperature, 0..+50 °C
Accuracy temperature ±1% of measuring range (typ. at 21 °C)
Inputs DI4: 4x input digital for floating switch contact
Switch range Berker S.1, B.3 aluminum, B.7 glass, Q.1, Q.3, , K.5 aluminum | stainless steel
Switch range Busch-Jaeger Busch-balance® SI, Busch-Duro 2000® SI, Reflex SI, solo® *, future® linear *, impuls, Busch-axcent® *, alpha nea®
Switch range Feller EDIZIOdue
Switch range Gira E2, E3, Standard 55, Esprit, Event, F100 *
Switch range Jung LS 990 *, A 500, AS 500, A plus, A creation, CD 500 *
Switch range Merten M-Smart, M-Plan, 1-M, Atelier-M, M-Pure, Artec *, Artec stainless steel *, Antik *
Switch range Peha AURA, AURA glass
Protection IP20 according to EN 60529
Ambient condition max. 85% rH non-condensing
Mounting flush mounted in standard EU box (Ø=60 mm, min. depth=45 mm)
Delivery contents software for configuration (freeware via download)
Notes * in switch program with intermediate frame, for other frame designs please request
Contact

Contact us:


Thermokon Sensortechnik GmbH
Platanenweg 1
35756 Mittenaar
Tel.: +49 2778 6960-0


Write email