RPF100+ active
Pendulum sensor for temperature measurement in large, high rooms and spaces like open space offices, arcades, production plants. Especially designed for control and display systems.
Measured values | temperature |
---|---|
Output voltage | TRV: 1x 0..10 V or 0..5 V, min. load 5 kΩ |
Output current | TRA: 1x 4..20 mA, max. load 500 Ω |
Power supply | TRV: 15..24 V = (±10%) or 24 V ~ (±10%) SELV, TRA: 15..24 V = (±10%) SELV |
Power consumption | TRV: typ. 0,4 W (24 V =) | 0,8 VA (24 V ~), TRA: max. 0,5 W (24 V =) |
Output signal range temp. | Scaling analog output, 0..+160 °C (default setting), selectable from 8 temperature ranges -50..+50 | -20..+80 | -15..+35 | -10..+120 | 0..+50 | 0..+100 | 0..+160 | 0..+250 °C, adjustable at the transducer |
Operating temperature range | permissible working temperature, -35..+70 °C |
Accuracy temperature | ±0,5 K (typ. at 21 °C within default measuring range) |
Enclosure | enclosure USE-S, PC, pure white |
Protection (IP) | IP65 according to EN 60529, SI-Protection |
Cable entry | Flextherm M20 for wire Ø=4,5..9 mm, removable |
Electrical connection | plug-in terminal, max. 2,5 mm², sensor wire white 1 m (default), 2 m, 4 m, 6 m, for other lengths please request |
stainless steel V2A, Ø=15 mm, mounting length 100 mm, hex pressed | |
Ambient condition | max. 85% rH short term condensation |
Delivery content | incl. mounting base enclosure USE-S pure white |