RDF18

Ceiling flush mounted sensor for temperature measurement in interior spaces to be mounted inconspicuously into ceiling panels thus providing an overall architectural picture.

Measuring valuestemperature
Output passivepassive temperature sensor
Measuring range temp.-35..+70 °C
Operating temperature rangepermissible working temperature, -35..+70 °C
Accuracy temperaturedepending on used sensor, PT100 | PT1000: ±0,3 K (typ. at 0 °C, Kl.B), Ni1000: ±0,4 K (typ. at 0 °C), Ni1000TK5000: ±0,4 K (typ. at 0 °C), NTC10K: ±0,22 K (typ. at 25 °C)
Sensor2-wire (standard)
ProtectionIP30 according to EN 60529
Connection electricalconnection wire PVC, 2x Ø=0,25 mm², grey, 1 m (default), 2 m, 4 m, 6 m, for other lengths please request
Sensor headABS, white, Ø=30 mm
Ambient conditionmax. 85% rH non-condensing
Mountingfacet mounting
Notesactive types for temperature and humidity available (see humidity – FT-RDF18+)
Contact

Contact us:


Thermokon Sensortechnik GmbH
Platanenweg 1
35756 Mittenaar
Tel.: +49 2778 6960-0


Write email


View contact