NOVOS 5 Temp active

Room sensor in the new Thermokon enclosure NOVOS 5 for measuring room temperature. The maintenance-free sensor creates the conditions for a pleasant indoor climate and well-being. Typical applications are schools, office buildings, hotels, cinemas or similar. The device has an LC display with color change function for displaying the measured values. The threshold values and display settings can be individually configured via the Thermokon NOVOSapp. For set point and fan stage adjustment, manual override for room and office applications please refer to NOVOS 5 x in 'Room Operating Units'.

Measuring valuestemperature
Output voltageTRV: 1x 0..10 V or 0..5 V, (live-zero configuration via Thermokon NOVOSapp), min. load 10 kΩ
Output ampereTRA: 1x 4..20 mA, max. load 500 Ω
Power supply15..35 V = or 19..29 V ~ SELV, TRA: 15..35 V = SELV
Power consumptiontyp. 0,6 W (24 V =) | 1,0 VA (24 V ~)
Output signal range temp.Scaling analog output, 0..+50 °C (default setting), selectable from 4 temperature ranges -50..+50 | 0..+50 | -20..+80 | -15..+35 °C, optionally configurable via Thermokon NOVOSapp
Operating temperature range-20..+70 °C
Accuracy temperature±0,5 K (typ. at 21 °C)
DisplayLCD 29x35 mm with RGB backlight
EnclosurePC V0, pure white, design cover (optional)
ProtectionIP30 according to EN 60529
Cable entryrear entry, breaking points bottom, drill mark top
Connection electricaltool-free mountable spring clamp, max. 1,5 mm²
Ambient conditionmax. 85% rH non-condensing
Mountingsurface mounted on flush-mounting box (Ø=60 mm), or to be mounted flat onto the surface using screws, base part can be mounted and wired separately
Notesfor configuration an optional programming dongle (Bluetooth) is available (refer to accessories)