Room sensor in the new Thermokon enclosure NOVOS 5 for measuring room temperature. The maintenance-free sensor creates the conditions for a pleasant indoor climate and well-being. Typical applications are schools, office buildings, hotels, cinemas or similar. The device has an LC display with color change function for displaying the measured values. The threshold values and display settings can be individually configured via the Thermokon NOVOSapp. For set point and fan stage adjustment, manual override for room and office applications please refer to NOVOS 5 x in 'Room Operating Units'.

Measuring values temperature
Output voltage TRV: 1x 0..10 V or 0..5 V, (live-zero configuration via Thermokon NOVOSapp), min. load 10 kΩ
Output ampere TRA: 1x 4..20 mA, max. load 500 Ω
Power supply 15..35 V = or 19..29 V ~ SELV, TRA: 15..35 V = SELV
Power consumption typ. 0,6 W (24 V =) | 1,0 VA (24 V ~)
Output signal range temp. Scaling analog output, 0..+50 °C (default setting), selectable from 4 temperature ranges -50..+50 | 0..+50 | -20..+80 | -15..+35 °C, optionally configurable via Thermokon NOVOSapp
Operating temperature range -20..+70 °C
Accuracy temperature ±0,5 K (typ. at 21 °C)
Display LCD 29x35 mm with RGB backlight
Enclosure PC V0, pure white, design cover (optional)
Protection IP30 according to EN 60529
Cable entry rear entry, breaking points bottom, drill mark top
Connection electrical tool-free mountable spring clamp, max. 1,5 mm²
Ambient condition max. 85% rH non-condensing
Mounting surface mounted on flush-mounting box (Ø=60 mm), or to be mounted flat onto the surface using screws, base part can be mounted and wired separately
Notes for configuration an optional programming dongle (Bluetooth) is available (refer to accessories)