NOVOS 5 Temp active
Active room sensor in the NOVOS 5 enclosure for temperature measurement. The maintenance-free sensor contributes to a pleasant room climate and well-being. Typical applications include schools, office buildings, hotels or cinemas. The NOVOS 5 uses an LCD with color-changing backlight for displaying the measured values and exceeding threshold values. Different parameters like the display settings can be individually configured via Thermokon NOVOSapp. Optionally, operating elements for controlling HVAC systems can be added (see product NOVOS 5 x in the chapter 'Room Operating Units').
Measured values | temperature |
---|---|
Output voltage | TRV: 1x 0..10 V or 0..5 V, (live-zero configuration via app or uConfig), min. load 10 kΩ |
Output current | TRA: 1x 4..20 mA, max. load 500 Ω |
Power supply | 15..35 V = or 19..29 V ~ SELV, TRA: 15..35 V = SELV |
Power consumption | typ. 0,6 W (24 V =) | 1,0 VA (24 V ~) |
Output signal range temp. | Scaling analog output, 0..+50 °C (default setting), selectable from 4 temperature ranges -50..+50 | 0..+50 | -20..+80 | -15..+35 °C, optionally configurable via app or uConfig |
Operating temperature range | -20..+70 °C |
Accuracy temperature | ±0,5 K (typ. at 21 °C) |
Display | LCD 29x35 mm with RGB backlight, Display and colours optionally configurable via app or uConfig |
Colour | pure white, black or aluminium |
Enclosure | PC V0, design cover pure white, black or aluminium |
Protection (IP) | IP30 according to EN 60529 |
Cable entry | rear entry, breaking points bottom, drill mark top |
Electrical connection | tool-free mountable spring clamp, max. 1,5 mm² |
Ambient condition | max. 85% rH non-condensing |
Mounting | flush-mounted on standard EU box (Ø=60 mm), or to be mounted flat onto the surface using screws, base part can be mounted and wired separately |
Notes | for configuration an optional programming dongle (Bluetooth) is available (refer to accessories) |