NOVOS 3 Temp active
Active room sensor in the NOVOS 3 enclosure for measuring room temperature. The maintenance-free sensor contributes to a pleasant room climate and well-being. Typical applications include schools, office buildings, hotels or cinemas. Optionally, operating elements for controlling HVAC systems can be added (see product NOVOS 3 x in the chapter 'Room Operating Units').
Measured values | temperature |
---|---|
Output voltage | 0..10 V or 0..5 V (live-zero can be configured via app or uConfig), min. load 10 kΩ |
Output current | 4..20 mA, max. load 500 Ω |
Power supply | 15..35 V = or 19..29 V ~ SELV, TRA: 15..35 V = SELV |
Power consumption | typ. 0,6 W (24 V =) | 1,0 VA (24 V ~) |
Output signal range temp. | Scaling analog output, 0..+50 °C (default setting), selectable from 4 temperature ranges -50..+50 | 0..+50 | -20..+80 | -15..+35 °C, optionally configurable via app or uConfig |
Accuracy temperature | ±0,5 K (typ. at 21 °C) |
Colour | pure white, black or aluminium |
Enclosure | PC V0, optionally with design cover black or aluminium |
Protection (IP) | IP20 according to EN 60529 |
Cable entry | rear entry, breaking points bottom, drill mark top |
Electrical connection | tool-free mountable spring clamp, max. 1,5 mm² |
Ambient condition | -35..+70 °C, max. 85% rH non-condensing |
Mounting | flush-mounted on standard EU box (Ø=60 mm), or to be mounted flat onto the surface using screws, base part can be mounted and wired separately |
Notes | for configuration an optional programming dongle (Bluetooth) is available (refer to accessories) |