RGS03 active
Immersion sensor (high temperature) with an integrated thermowell pocket for temperature measurement of liquids in HVAC applications. Also suited to be installed in exhausts. Designed for connection to superior control systems.
Measured values | temperature |
---|---|
Medium | gases, fluids |
Output voltage | TRV: 1x 0..10 V |
Output current | TRA: 1x 4..20 mA |
Power supply | TRV: 15..35 V = or 15..26 V ~ SELV, TRA: 15..24 V = (±10%) SELV |
Power consumption | TRV: typ. 1 W (24 V =) | 1,4 VA (24 V ~), TRA: typ. 0,5 W (24 V =) |
Output signal range temp. | Scaling analog output, type-dependent, TRV6 | TRA6: 0..+400 °C, TRV7 | TRA7: 0..+600 °C |
Operating temperature range | permissible working temperature, pocket 0..+500 °C, temporarily up to +600 °C, enclosure: -35..+70 °C |
Accuracy temperature | ±0,2 K ±0,1% of measured value (typ. at 21 °C) |
Enclosure | shape B, aluminium |
Protection (IP) | IP66 according to EN 60529 |
Cable entry | M20 for wire max. Ø=8 mm |
Electrical connection | terminal block, max. 1,5 mm² |
Neck pipe | stainless steel V2A |
stainless steel V4A, Ø=9 mm, thread G 1/2", mounting length: 250 | 500 mm | |
Ambient condition | max. 85% rH short term condensation |