RG03 active

Duct sensor (high temperature) for temperature measurement of liquids in duct applications for heating, ventilation and air-conditioning. Also suitable for exhaust systems.

Measuring values temperature
Output voltage TRV: 1x 0..10 V, min. load 3 kΩ
Output ampere TRA: 1x 4..20 mA, max. load 500 Ω
Power supply 15..24 V = (±10%) SELV
Power consumption TRV: max. 1 W (24 V =), TRA: max. 0,5 W (24 V =)
Output signal range temperature TRV | TRA:, Scaling analog output, type-dependent, TRV6 | TRA6: 0..+400 °C, TRV7 | TRA7: 0..+600 °C
Operating temperature range pocket 0..+500 °C, temporarily up to +600 °C, enclosure: -35..+70 °C, permissible working temperature
Accuracy temperature ±0,2 K ±0,1% of measured value (typ. at 21 °C)
Enclosure shape B, aluminium
Protection IP66 according to EN 60529
Cable entry M20 for wire max. Ø=8 mm
Connection electrical terminal block, max. 1,5 mm²
Pocket stainless steel V4A, Ø=11 mm, mounting length: 250 | 500 mm
Ambient condition max. 85% rH short term condensation
Weight 400 g
Delivery contents incl. mounting flange
Contact

Contact us:


Thermokon Sensortechnik GmbH
Platanenweg 1
35756 Mittenaar
Tel.: +49 2778 6960-0


Write email


View contact