MWF400+ relay / LCD / BUS
Duct sensor for measuring the average temperature in air ducts. The sensor measures the current mean temperature value throughout the entire length. A spring at the connection head reduces vibrations. Mounting angles are included in the delivery content. Models with a relay output for a 2-point controller or a 2-stage 2-point controller and color-changing LCD allow for a wide range of applications. Depending on the model, the sensor can be individually configured via Thermokon USEapp. A hinged cover and tool-free wiring as well as removable cable entries ensure quick and easy installation.
Measured values | temperature |
---|---|
Output voltage | 0..10 V or 0..5 V (adjustable via jumper; live-zero configuration via app or uConfig), min. load 5 kΩ |
Output current | TRA: 1x 4..20 mA, max. load 500 Ω |
Output switch contact | Relay: 2x floating contact NO for 24 V ~ or 24 V = / 3 A, optional |
Network technology | RS485 BACnet (MS/TP), LON FT (free topology), RS485 Modbus |
Power supply | 15..35 V = or 19..29 V ~ SELV, A: 15..35 V = SELV |
Power consumption | max. 2,5 W (24 V =) | 4,3 VA (24 V ~) |
Output signal range temp. | Scaling analog output, -20..+80 °C (default setting), selectable from 8 temperature ranges -50..+50 | -20..+80 | -15..+35 | -10..+120 | 0..+50 | 0..+100 | 0..+160 | 0..+250 °C, optionally configurable via app or uConfig |
Operating temperature range | permissible working temperature, sensor rod -30..+80 °C, enclosure: -35..+70 °C, LCD: -20..+70 °C |
Accuracy temperature | ±0,5 K (typ. at 21 °C within default measuring range) |
Display | LCD 29x35 mm with RGB backlight, optional |
Enclosure | enclosure USE-M, PC, pure white, LCD: cover PC, transparent |
Protection (IP) | IP65 according to EN 60529 |
Cable entry | Flextherm M20 for wire Ø=4,5..9 mm, Relay/BUS: M25 with fourfold cable entry for wire with max. Ø=7 mm, removable |
Electrical connection | removable plug-in terminal, max. 2,5 mm², BUS terminal: removable plug-in terminal, max. 1,5 mm² |
Sensor rod | copper, Ø=4 mm, mounting length 400 mm, Sensor neck: stainless steel V4A, Ø=6 mm |
Ambient condition | max. 85% rH short term condensation |
Delivery content | incl. mounting flange MF6DS flexible |