KFK03 passive

Duct sensor for measuring air temperature and other gaseous media for HVAC applications (e.g. in supply and exhaust ducts).

Measuring values temperature
Output passive PT100 | PT100 1/3 DIN | PT1000 | PT1000 1/3 DIN | Ni1000 | Ni1000TK5000, NTC10k | NTC 10k Precon | NTC20k | NTC1,8k, LM235Z
Measuring range temp. PT / Ni: -50..+160 °C (T160), optional -80..+260 °C (T260), NTC: -50..+150 °C (T150), LM235Z: -50..+120 °C (T120)
Operating temperature range passive: depending on used sensor, optional -80..+260 °C (T260), enclosure: -35..+90 °C, permissible working temperature
Accuracy temperature depending on used sensor
Sensor 2-wire (standard), 3-wire or 4-wire
Enclosure shape B, aluminium
Protection IP66 according to EN 60529, SI-Protection (not possible for electronic Sensors)
Cable entry M20 for wire max. Ø=8 mm
Connection electrical terminal block, max. 1,5 mm²
Pocket stainless steel V4A, Ø=8 mm, mounting length: 100 | 150 | 200 | 250 mm
Ambient condition max. 85% rH short term condensation
Weight 250 g
Mounting for duct sensors please use mounting flange MF8 (VA), for immersion sensors please use immersion pocket THVA / THMS
Notes other temperature sensors on request
Contact

Contact us:


Thermokon Sensortechnik GmbH
Platanenweg 1
35756 Mittenaar
Tel.: +49 2778 6960-0


Write email


View contact