KFK01

Passive duct sensor for measuring air temperature and other gaseous media for HVAC applications (e.g. supply and exhaust ducts).

Measuring values temperature
Output passive PT100 | PT100 1/3 DIN | PT1000 | PT1000 1/3 DIN | Ni1000 | Ni1000TK5000, NTC10k | NTC 10k Precon | NTC5k | NTC20k | NTC1,8k, LM235Z
Measuring range temp. depending on used sensor, PT / Ni: -50..+160 °C (T160), NTC / KTY: -50..+150 °C (T150), LM235Z: -50..+120 °C (T120)
Operating temperature range passive: depending on used sensor, optional -80..+260 °C (T260), enclosure: -35..+90 °C, permissible working temperature, pocket -50..+160 °C
Accuracy temperature depending on used sensor
Sensor passive: 2-wire (standard), 3-wire or 4-wire
Enclosure shape J, aluminium
Protection IP65 according to EN 60529
Cable entry M16 for wire max. Ø=8 mm
Connection electrical terminal block, max. 1,5 mm²
Pocket stainless steel V4A, Ø=6 mm, mounting length: 50 | 100 | 150 | 200 | 250 | 300 | 450 mm
Ambient condition max. 85% rH short term condensation
Mounting for duct sensors please use mounting flange MF6DS flexible or MF6 (brass), for immersion sensors please use immersion pocket THVADS / THMSDS
Notes for mounting up to +260 °C Mounting flange MF6 (brass) is recommended
Contact

Contact us:


Thermokon Sensortechnik GmbH
Platanenweg 1
35756 Mittenaar
Tel.: +49 2778 6960-0


Write email


View contact